CMS200
6.3.15 Fan cycle on (FCO)
Display
Description
Considerations
Range
Global default
6.3.16 Fan cycle off (FCF)
Display
Description
Considerations
Range
Global default
6.3.17 Alarm delay (Ad)
Display
Description
Considerations
Range
Global default
www.nexo.com
Defines the active period of the evaporator fan while the compressor is switched off.
Fan cycle is the fan cycle on (FCO) time + the fan cycle off (FCF) time.
1 to 30 minutes
5 minutes
Defines the inactive period of the evaporator fan while the compressor is switched off.
Fan cycle is the fan cycle on (FCO) time + the fan cycle off (FCF) time.
0 to 30 minutes
20 minute
Defines the maximum time the cooler door can be open before sounding the alarm
buzzer.
If disabled, the door switch is also disabled - if so the controller does not detect door
openings therefore, it does not:
• Update the self-learning matrix for door activity.
• Manage the evaporator fan for door activity.
• Sound door alarms if the door is left open.
0 to 30 minutes
0 (disabled)
Page 51