7.5.2
Make the grid connection
4-core connection, TN-C system
↻ Grid connection is prepared.
1 Connect lines in accordance with the labels on the name plate on the screw ter-
minal [ T_45/
10 Nm].
2 Check secure fit of all connected cables.
3 Tighten the cable fittings [ W_66 /
» The device is connected to the power grid.
NOTE
An AC-side disconnection unit must be provided during the final installation stage. This disconnecter mech-
anism must be installed so that it can be accessed at any time without obstruction.
NOTE
If a residual current circuit breaker is necessary due to the installation specification, a type A residual cur-
rent circuit breaker must be used.
If the type A is used, the insulation threshold must be set to greater than/equal to (≥) 200kOhm in the
"Parameters" menu Menu.
For questions regarding the appropriate type, please contact the installer or our KACO new energy cus-
tomer service.
NOTE
When the line resistance is high, i.e. long cables on the grid side, the voltage at the grid terminals of the
device will increase in feed-in mode. If the voltage exceeds the country-specific grid overvoltage limit
value, the device switches off.
Ensure that the cable cross-sections are sufficiently large or that the cable lengths are sufficiently
short.
7.6
Connect PV generator to device
7.6.1
Configuring the DC plug connector
a
b
d
2
1
c
5
6
Fig. 20: Insert wires
Key
1
Wire for DC connection
2
Spring
3
Insert
4
Sleeve
↻ Connection area opened.
↻ NOTE: Before proceeding with the isolation ensure that you do not cut any individual wires.
Page 22
13 Nm].
3
4
Fig. 21: Slide insert into sleeve
5
Cable fitting
6
Contact plug
7
Coupling
Fig. 19: 4-pole connection
7
Fig. 22: Check fastening
KACO blueplanet 50.0 TL3