Operation Instruction
nEnglish translation of German original
Authorised electrician
Important safety instructions
These instructions form part of the product and must be carefully read, observed and stored in a place which is freely accessible at all
times.
Kaco blueplanet 50.0TL3
S, Basic, M, L, XL, XL-FR

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Blueplanet 50.0TL3 S and is the answer not in the manual?

Questions and answers

Summary of Contents for Kaco Blueplanet 50.0TL3 S

  • Page 1 Kaco blueplanet 50.0TL3 S, Basic, M, L, XL, XL-FR Operation Instruction nEnglish translation of German original Authorised electrician Important safety instructions These instructions form part of the product and must be carefully read, observed and stored in a place which is freely accessible at all...
  • Page 2 Legal provisions The information contained in this document is the property of KACO new energy GmbH. Publication, in whole or in part, requires the written permission of KACO new energy GmbH. KACO warranty For current warranty conditions contact your system integrator.
  • Page 3: Table Of Contents

    Manual Photovoltaic feed-in inverter Contents General information............ 4 Configuration and operation .......... 35 About this document.......... 4 Initial start-up ............  35 More information............ 4 Controls..............  35 Layout of Instructions.......... 5 User interface ............  37 Identification .............  6 Menu structure ............  38 Warnings on the device..........
  • Page 4: General Information

    Storing the documents These instructions and other documents must be stored near the system and be available at all times. ž The current version of the operating Instructions can be downloaded from www.kaco-newenergy.com. English translation of German original This document has been produced in several languages. The German-language version is the original version. All other language versions are translations of the original version.
  • Page 5: Layout Of Instructions

    Information that is important for a specific topic or objective, but that is not safety-relevant. 1.3.4 Symbols for instructions ↻ Prerequisite for use 1 Carry out the next step 2 Additional action sequence ð Interim result of the action » End result Kaco blueplanet 50.0TL3 Page 5...
  • Page 6: Identification

    Identification You will find the name plate with the following data for service and other require- KACO blueplanet 50.0 TL3 M1 WM OD IIGX Part number 1001430 Serial number 50.0TL01654321 Year Q1 / 16 KACO new energy ments specific to installation on the right side panel of the product: Carl-Zeiss-Straße 1...
  • Page 7: Safety

    Standard Harmonised document - HD 60364-7-712 (European im- plementation of the IEC standard) PV section of NEC 690 and sections in article 100, 690.4, 690.6 and 705.10 Tab. 1: Examples of standards specific to business premises Kaco blueplanet 50.0TL3 Page 7...
  • Page 8: Protection Features

    The device is intended for indoor and outdoor applications and may only be used in countries for which it has been ap- proved or for which it has been released by KACO new energy and the grid operator. Operate the device only with a permanent connection to the public power grid. The country and grid type selection must be commensurate with the respective location and grid type.
  • Page 9: Description Of The Device

    F Switch the DC isolator switches from 0 (OFF) to 1 (ON). Fig. 5: DC isolator switch 3.2.2 Electrical functions A potential-free relay contact is integrated into the device. Use this contact for one of the following functions: Kaco blueplanet 50.0TL3 Page 9...
  • Page 10 Digital inputs You can extend the unit with additional digital inputs by means of an extension module (available from KACO customer service). This can be used to connect a ripple control receiver or a protective shutdown system.
  • Page 11: System Layout

    The reference counter is to be specified and installed by the power supply company. This measures the amount of en- ergy drawn. Device version S: An external DC isolator switch is required outside the devices. Kaco blueplanet 50.0TL3 Page 11...
  • Page 12: Technical Data

    The connected PV-Generator must be designed, that the max short circuit current is below or equal to ISCmax of the inverter under all foreseeable conditions. In no condition the design may result in a greater short cir- cuit current than ISCmax of the inverter.Designing the PV generator [See section 7.6.4} Page 27]. Page 12 Kaco blueplanet 50.0TL3...
  • Page 13: General Data

    HUGX IIGX FRGX General Data Display Graphical display 240 x 128 pixels + LEDs Controls 4-way button + 2 buttons Menu languages DE; EN; FR; IT; ES; PL; NL; PT; CZ; HU; SL; TR; RO Kaco blueplanet 50.0TL3 Page 13...
  • Page 14: Environmental Data

    Power derating from 50 °C +50 °C Protection rating (KACO installa- IP65 tion location) Humidity range (non-condensing) 100% For installation in aggressive environmental conditions (e.g. possibility of corrosion), you must contact the KACO Sales team (pv-projects@kaco-newenergy.de). Page 14 Kaco blueplanet 50.0TL3...
  • Page 15: Transportation And Delivery

    Code (s) Shape of the connector Tightening torque External hexagon Spanner size or number Internal hexagon Torx Outer contour Slot Fig. 8: Form pattern Tab. 2: Key and description of tool codes Kaco blueplanet 50.0TL3 Page 15...
  • Page 16: Assembly And Preparation

    ž Must be accessible for installation and maintenance ž Must be made out of heat-resistant material (up to 90 °C ) ž Must be flame resistant ž Minimum clearances to be observed during installation: [See figure 14] [} Page 18] Page 16 Kaco blueplanet 50.0TL3...
  • Page 17: Unpacking The Device

    2 Pull the clamp off the packaging. 3 Pull the hood upwards to remove it and place the cardboard packaging to one side together with the mount and ac- cessories. 4 Set the unit with base and side sections upright. Kaco blueplanet 50.0TL3 Page 17...
  • Page 18: Fastening The Mount

    3 Fix the mount to the wall using suitable mounting fixtures from the mounting kit. NOTE: Make sure that the mount is oriented correctly. » Proceed with the installation of the device. Page 18 Kaco blueplanet 50.0TL3...
  • Page 19: Installing And Securing The Device

    The outer contour of the mount must be flush with the outer contour of the housing. 3 Insert the screw provided into the lug of the mount and secure the device to prevent it from being lifted off [ T30 / 2 Nm]. ( [See figure 13] [} Page 18]). Kaco blueplanet 50.0TL3 Page 19...
  • Page 20 Seal off any plug-in connections and screw fittings using sealing covers. › Prior to installation, check the inner area for condensation and if necessary, allow it to dry sufficiently before installation. › Immediately remove any moisture from the housing. Page 20 Kaco blueplanet 50.0TL3...
  • Page 21: Installation

    Surveying the connection area The connection for the AC supply is located inside the housing. The DC input source is connected either inside or outside the housing depending on the device version (S, Basic, M or XL). Kaco blueplanet 50.0TL3 Page 21...
  • Page 22: Making The Electrical Connection

    1.8 - 2.75 (2mm² - 6mm²) mm cable fitting Fitting for DC connec- SW15 tion Torque for cable fit- 4 Nm 1.8 Nm ting AC-side Max. conductor cross-section 95 mm² Max. cable cross-section (without wire sleeves) 95 mm² (AL or CU) Page 22 Kaco blueplanet 50.0TL3...
  • Page 23: Connecting The Device To The Power Grid

    RJ45 Torque for cable fitting 4 (M25) 1.5 (M16) Nm Overvoltage protection Type [KACO article no.] Overvoltage of DC plugs (integrated in XL version) VAL-MS-T1/T2 1000DC-PV-ST - 2801162 [3010608] - SPD I + II VAL-MS 1000DC-PV-ST – 2800624 [ ] - SPD II Overvoltage protection for AC plug (option) 7P.10.8.275.0012 [3010610] –...
  • Page 24 2 Lay the grounding cable onto the grounding point. Secure using the corresponding nut and lock washer [ W_13/ 10 Nm]. 3 Connect wires in accordance with the labels on the screw terminal [ T_45 / 10 Nm]. 4 Check secure fit of all connected cables. Page 24 Kaco blueplanet 50.0TL3...
  • Page 25: Connect Pv Generator To Device

    If the type A is used, the insulation threshold must be set to greater than/equal to (≥) 200kOhm in the “Parameters” menu Menu [See section 9.4.1} Page 38]. For questions regarding the appropriate type, please contact the installer or our KACO new energy cus- tomer service.
  • Page 26 Model Recommended fuses Quantity KACO blueplanet 50.0 TL3 M1 WM OD IIGX PV- Fuse 14 x 51 mm1100V gPV max. 20A ↻ Suitable string fuse has been selected. ↻ NOTE: DC fuses can be ordered from our customer service team. Use PV fuses only.
  • Page 27 The device is designed with a reserve of DC short-circuit current withstand capability. This allows oversizing of the connected PV generator. The absolute limit for the PV generator is the value of the maximum short circuit current (lsc max) and maximum open circuit voltage (Uoc max). Kaco blueplanet 50.0TL3 Page 27...
  • Page 28 PV generator. Fig. 34: Connection to XL version NOTE: Meet the requirements of protection class IP65 by closing the unused plug connectors with protective caps. » The device is connected to the PV generator. Page 28 Kaco blueplanet 50.0TL3...
  • Page 29: Inserting The Overvoltage Protection

    Make sure that no moisture or dust impacts on the circuit board during installation. Moisture and dust particles must be removed immediately. In doing so, disassembly of the circuit board may be neces- sary. All interfaces are located on the communication circuit board on the inside of the housing door. Kaco blueplanet 50.0TL3 Page 29...
  • Page 30 The connection plug of an RJ45 cable is larger than the opening of an M25 cable fitting when it is installed. For this reason, remove the sealing insert before installation and thread the Ethernet cable outside of the cable fitting through the sealing insert. Page 30 Kaco blueplanet 50.0TL3...
  • Page 31 Recommendation Li2YCYv (twisted pair) black for laying cable outside and in the ground, 2 x 2 x 0.5 mm² Li2YCY (twisted pair) grey for dry and damp indoor spaces, 2 x 2 x 0.5 mm² Kaco blueplanet 50.0TL3 Page 31...
  • Page 32 The digital input of the device is intended for connection of a Powador-protect. When using devices from other manufacturers or in combination with KACO inverters, interface switches as a minimum must be used for shutting down devices from other manufacturers.
  • Page 33: Sealing The Connection Area

    Powador- ↻ Only suitable KACO inverters can be used. RS485 protect ↻ Housing doors open. BA BA GND GND 1 Undo the cable fittings [ W_20] 2 Pass the connecting cable through the cable fittings. RS485 3 Connect wire A (+) to the terminal marked "EVU+" on the first device via the INV Signal "DO1"...
  • Page 34: Commissioning

    - Réseau de distribution F Attach the provided safety sticker to the outside of the device housing where it is -Panneux photovoltaïques clearly visible. Fig. 42: Safety label UTE C15-712-1 Page 34 Kaco blueplanet 50.0TL3...
  • Page 35: Configuration And Operation

    The "Feed-in" icon appears on the LD display. The device feeds into the grid. *) The waiting period ensures that the generator voltage continuously remains above the power delivery limit of 200 V. For country-specific waiting periods see our website. Kaco blueplanet 50.0TL3 Page 35...
  • Page 36 ↻ You have left the desktop. The device displays the menu. F Use the up button or down button to navigate. Opening a menu item or a setting F Use the right arrow button and the Enter button. Page 36 Kaco blueplanet 50.0TL3...
  • Page 37: User Interface

    In normal operation, the backlighting is switched off. As soon as you press one of the control buttons, the backlighting is activated. If no button is pressed for an adjustable period of time, the backlighting switches off again. You can also activ- ate or disable the backlighting permanently. Kaco blueplanet 50.0TL3 Page 37...
  • Page 38: Menu Structure

    Functions restricted to one or more countries are labelled with country codes in accordance with ISO 3166-1. Symbols used Menu level (0,1,2,3) Password-protected menu (password can be re- quested from KACO customer service) Display Submenu Option menu Option box Setting range 9.4.1...
  • Page 39 » Press any button to return to the previous menu. CSV log data F Open the menu: Press the Right arrow button or Enter button. Decimal separator F Select decimal sign for export of saved operating data. Kaco blueplanet 50.0TL3 Page 39...
  • Page 40 1 Configure the contrast setting for the display. 2 Set the length of time without user input after which the backlight- ing of the LCD switches off. 3 Alternatively: Permanently activate or disable the backlighting by selecting "On" or "Off". Page 40 Kaco blueplanet 50.0TL3...
  • Page 41 NOTE: The menu options "Write access" and "Port" are only dis- played with TCP activated. 1 Activate Modbus TCP. Write access F Allow Modbus TCP write access. Port F Set network port. Connection status Indicates the status of the network connection. Kaco blueplanet 50.0TL3 Page 41...
  • Page 42 On/Off Country NOTE: This option influences the country-specific operating settings of the device. Please consult KACO service for further information. 1 Enter the four-digit password using the 4-way button. The password is unit-specific. 2 Confirm the entry with the Enter button.
  • Page 43 If the value f> (slow overfrequency shutdown) is set to a value which is smaller than the value of f (maximum restart frequency) using the max. LC display, then the value of f is automatically set to the value of max. f>. Kaco blueplanet 50.0TL3 Page 43...
  • Page 44 Specify stage 0-3 b.) Specify stage 4-7 c.) Specify stage 8-11 d.) Spe- cify stage 12-15 4 Confirm the entry with the Enter button. Fault ride-through NOTE: The device doesn't support dynamic grid stabilization (Fault Ride-Through). Page 44 Kaco blueplanet 50.0TL3...
  • Page 45 F Specify output gradient increase and decrease in Outg. grad. (per thousand). Deact. grad. F Specify deactivation gradient in (per thousand) /minute (if mode "1" or mode "2" is active. This menu option is displayed permanently for IT and IL!). Kaco blueplanet 50.0TL3 Page 45...
  • Page 46 Over-excited | un- phase shift. der-excited Q(U) 10 nodes F Open the menu: Press the Right arrow button or Enter button. NOTE: More detailed information about the procedure can be found Reactive power control [See section 10.1} Page 58] Page 46 Kaco blueplanet 50.0TL3...
  • Page 47 F Reset active curve to the default setting. Reset the curve Number of nodes NOTE: The maximum number of configurable nodes depends on the selected grid type. 2 - 10 F Specify the number of nodes for the Q(U) characteristic curve. Kaco blueplanet 50.0TL3 Page 47...
  • Page 48 DC voltage. 1 Activate or disable the constant voltage controller. 2 Set value for constant voltage controller. F Set threshold value (in 1kOhm increments) at which the insulation Iso.resistor monitor reports a fault. Page 48 Kaco blueplanet 50.0TL3...
  • Page 49 F Set reference voltage for the active control process. Reference voltage U< - U> F Set voltage range for the active control process. Minimum operating voltage 45 – 125.0 [% Unom] & Maximum operating voltage 45 – xxx [% Unom] Password protection Status Kaco blueplanet 50.0TL3 Page 49...
  • Page 50 Advanced islanding detection [See section 10.5} Page 73] F Activate passive grid influence by application of a frequency. ROCOF operation mode passive Off | F Activate active grid influence by application of a frequency. ROCOF operation mode active Off | Page 50 Kaco blueplanet 50.0TL3...
  • Page 51 This may be necessary in order to limit the maximum power rating of the system at the grid connection point, upon the grid operator's request. Internal NOTE: Opportunity to limit the power internally Power Limitation F Specify the activation status. Status Kaco blueplanet 50.0TL3 Page 51...
  • Page 52 1 Set frequency thresholds for activating the power limitation with with overfrequency overvoltage. 50.2 – 70 (Hz) 2 Set the frequency thresholds for activating the power limitation Activation threshold with undervoltage. with underfrequency 40 – 45 (Hz) Page 52 Kaco blueplanet 50.0TL3...
  • Page 53 NOTE: If the 10 min mean value of the voltage exceeds the activation threshold, then the function is enabled. The power level is adjusted in such a way that the instantaneous effective voltage value does not ex- ceed the activation threshold value. Kaco blueplanet 50.0TL3 Page 53...
  • Page 54: Monitoring The Device

    F Load a set of parameters from external storage media. meters NOTE With regard to the selection of country settings, KACO new energy attests: › that the relevant certificates are only valid if the corresponding country settings have been selected.
  • Page 55 3 To show or hide measurements, select or deselect the corresponding checkboxes in the “Choose view” area. Exporting data 1 Filter the display data if necessary. 2 Select the display period if applicable (daily, monthly, yearly or overview). 3 Press the “Export data” button. 4 Save the file. Kaco blueplanet 50.0TL3 Page 55...
  • Page 56: Performing A Firmware Update

    Never disconnect the DC and AC power supply for or during a firmware update. › Do not remove the USB stick during the firmware update. Preparing a firmware update 1 Download the firmware update file from the KACO web site www.kaco-newenergy.com and store it on your hard disk.
  • Page 57: Access Via Modbus

    1 Enable the entry Network – Modbus TCP - Operation mode / Network services – Modbus TCP - Operation mode in the menu on the device or on the web interface. 2 If necessary, allow write access. 3 Set up the Port for access. [Default: 502] » Access via Modbus enabled. Kaco blueplanet 50.0TL3 Page 57...
  • Page 58: Specifications

    10.1.3 Reactive power functions The following functions for controlling the reactive power are implemented in the devices listed above: ž cos φ constant ž Q constant ž cos φ /(p/pn) Page 58 Kaco blueplanet 50.0TL3...
  • Page 59 (PT-1) with a time constant of Tau=200ms. The specified displacement factor may be configured in the display or via communication, via KACO RS485 protocol and MODBUS/SunSpec. If the applicable grid code requires the cos-φ response to set point by a defined gradient or settling time slower than the configured Tau=200ms, this gradient or settling time must be implemented in the plant control system.
  • Page 60 Q(U) 10 nodes Lock-in power Power threshold, function is activated if limit value is exceeded. 0 – 100 [% S Lock-out power Power threshold, function is activated if limit value is undershot. 0 – 100 [% S Page 60 Kaco blueplanet 50.0TL3...
  • Page 61 1 – 0.3 Reactive power of the node as a percentage of the maximum power Over-excited | under- Reactive power mode Under-excited relates to inductive load, over-ex- excited cited relates to capacitive load. Kaco blueplanet 50.0TL3 Page 61...
  • Page 62: Active Power Regulation

    Otherwise, the set value will be used. Irrespective of the communication protocol used, the settling time “WMaxLim_Ena” is used in order to transfer the new power value. Otherwise, the internally configured value will be used. Page 62 Kaco blueplanet 50.0TL3...
  • Page 63 100%. The power limit follows the characteristic curve, a straight line between dp2 and dp3. However, because hysteresis is activated, the power limit is not increased when the voltage drops. The function is deactivated as soon as the voltage falls below dp1. Kaco blueplanet 50.0TL3 Page 63...
  • Page 64 With a voltage change, the active power is changed 100 – 1200000 [ms] according to a PT-1 characteristic curve with a settling time of 5 Tau. Note: The settling time is overlaid with the increasing and decreasing gradient. Page 64 Kaco blueplanet 50.0TL3...
  • Page 65 Equation 1 [See figure 54] [} Page 65] defines the maximum limit with ΔP relevant to 2 [See figure 55] [} Page 65], P the current power at the time of activation and P the reference power. In the case of PV inverters from KACO, P defined as P , the current power at the time of activation.
  • Page 66 Actual power | for overfrequency incidents. Nominal power Power reference with underfrequency: Power reference mode Power reference for power adjustment as in equation 6 and equation 7 with underfrequency for overfrequency incidents. Actual power | Nominal power Page 66 Kaco blueplanet 50.0TL3...
  • Page 67 Note 2: This function is stipulated as a requirement by some domestic grid connection directives in order to prevent any negative impact on is- land detection. However, P(f) has no negative impact on KACO's en- hanced island detection. Frequency of the max-...
  • Page 68: Frt

    If a reduction in power occurs, the power is brought back up to the pre-fault level within 100 ms of the voltage returning. Page 68 Kaco blueplanet 50.0TL3...
  • Page 69 For the positive and negative phase sequence voltage, Δu equates to the difference between the pre-fault voltage and the current voltage based on the reference voltage. The pre-fault voltage is calculated as a 1-min mean value. Fig. 63: Formula no. 3 Kaco blueplanet 50.0TL3 Page 69...
  • Page 70 Amplification factor for the negative sequence used in the calculation of quence dip the reactive current using formulae (2) and (4) Can be configured inde- pendently for drops and spikes. Constant k negative se- quence swell k 0 – 10 Page 70 Kaco blueplanet 50.0TL3...
  • Page 71: Other Grid-Supporting Functions That Are Effective In The Case Of Active Power

    The device capacity of a plant can be set to the exact agreed value using the S and P settings. To en- sure that the load on the devices in the plant is uniform, we recommend distributing the performance reduction evenly across all devices. Kaco blueplanet 50.0TL3 Page 71...
  • Page 72 Some grid connection rules insist that the agreed reactive power be supplied from every operating point of the plant without a reduction in the actual active power. Considering the fact that all KACO TL3 inverters have a semi-circular P-Q operating range, a reduction in the active power is, however, required during operation at maximum active power be- cause an apparent power reserve is not available.
  • Page 73: Advanced Islanding Detection

    Enhanced island detection method The enhanced island detection of KACO new energy, employs a strategy to reliably detect island formation that is based on the characteristic differences between an interconnected grid and an islanded grid, thus ensuring reliable fast detec- tion and prevention of false tripping.
  • Page 74 In the event of active stage 1, the device switches to zero current mode, and re- starts the infeed after a few 100ms. At stage 2, the device has shut down and the set reconnection conditions apply. Page 74 Kaco blueplanet 50.0TL3...
  • Page 75: Maintenance And Troubleshooting

    WARNING! Do not use compressed air or high-pressure cleaners! 1 Use a vacuum cleaner or a soft brush to remove dust from the fan cover and from the top of the device on a regular basis. Kaco blueplanet 50.0TL3 Page 75...
  • Page 76: Replacing The Fan

    4 Fit the fastening for the fan safety grille [ T_20 & W_ 7 / 2.5 Nm]. Fastening for fan 5 If required, fit another fan. Base plate » Switching on the device Commissioning [See section 8} Page 34]. Connector plug Connection socket Page 76 Kaco blueplanet 50.0TL3...
  • Page 77: Replacing The String Fuses

    Replacing the string fuses 1 Remove defective DC fuse from the fuse holder. NOTE: DC fuses can be ordered from the KACO customer service team. 2 Insert DC fuse of the same type into the fuse holder. 3 Ensure the DC fuse holder is completely closed after fitting.
  • Page 78: Overvoltage Protection

    Disconnecting connections 11.7.1 AC connection ↻ It has been ensured that there is no AC/DC voltage present. 1 Unlock and open the housing door. 2 Unfasten the cables (L1/L2/L3/N/PEN) from the AC connection terminal [ T_45]. Page 78 Kaco blueplanet 50.0TL3...
  • Page 79: Faults

    Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched. › If a fault occurs, notify an appropriately authorized and qualified electrician or KACO new energy GmbH Service. ›...
  • Page 80 (after the start-up period is complete), the device’s hardware is probably damaged. › Contact KACO Service to test the hardware. The device is displaying Faults in the grid. The device continues to operate as normal without losses to...
  • Page 81: Fault Messages

    B = Operator’s responsibility ; E = The indicated work may only be carried out by an authorised electrician. ; K = The indic- ated work may only be carried out by a service employee of KACO new energy GmbH! 11.9...
  • Page 82 "External grid been tripped. tion. Notify your au- protection shutdown" thorised electrician if the fault occurs repeatedly! Resid. current shutdown Residual current was detected. The feed-in Notify your author- was interrupted. ized electrician! Page 82 Kaco blueplanet 50.0TL3...
  • Page 83 Grid failure overvoltage L1 The voltage of a grid phase is too low; the grid Notify your author- cannot be fed into. The phase experiencing ized electrician! failure is displayed. Kaco blueplanet 50.0TL3 Page 83...
  • Page 84 The measured phase-to-phase voltage is out- Check software ver- voltage side of the tolerance limits. sion (possible can- cellation during up- load) Notify KACO Service! Grid failure underfrequency Grid frequency is too low. This fault may be Notify your author- grid-related. ized electrician! Grid failure overfrequency Grid frequency is too high.
  • Page 85 Buffer 1 self test error The control board is defective. Notify authorised electrician / KACO Service! Self test error buffer 2 The control board is defective. Notify authorised electrician / KACO Service! Relay 1 self test error The power section is defective.
  • Page 86 Ob- serve application note on the KACO website: Installing overvoltage protec- tion. NOTE Fault number not found? If fault numbers are displayed on the device but are not listed here, then it is usually necessary to have this looked at by your installation partner.
  • Page 87: Decommissioning And Dismantling

    XL device version: Disconnect all DC connections one by one. Device version S, Basic and M: Detach DC connection in the device. WARNING Risk of burns caused by hot housing components Housing components can become hot during operation. › During operation, only touch the housing cover on the device. Kaco blueplanet 50.0TL3 Page 87...
  • Page 88: Uninstalling The Device

    Prior to installation, check the inner area for condensation and if necessary, allow it to dry sufficiently before installation. ↻ Device packaged. F Store the device at a dry location, in accordance with the ambient temperature range Environmental data [See sec- tion 4.3} Page 14]. Page 88 Kaco blueplanet 50.0TL3...
  • Page 89: Disposal

    Unit: Do not dispose of faulty devices or accessories together with household waste. Ensure that the old devices and any accessories are disposed of in a proper manner. Packaging: Ensure that the transport packaging is disposed of properly. Kaco blueplanet 50.0TL3 Page 89...
  • Page 90: Service And Warranty

    Service and warranty If you need help solving a technical problem with one of our KACO products, please contact our service hotline. Please have the following information ready so that we can help you quickly and efficiently: ž Device name / serial number ž...
  • Page 91: Appendix

    Unauthorised modifications to the supplied devices and/or any use of the devices that is contrary to their intended use render this Declaration of Conformity null and void. This declaration of conformity is issued under the sole responsibility of KACO new energy GmbH. Kaco blueplanet 50.0TL3...
  • Page 92 Carl-Zeiss-Strasse 1 · 74172 Neckarsulm · Germany · Tel. +49 7132 3818-0 · Fax. +49 7132 3818-703 · info@kaco-newenergy.de · www.kaco-newenergy.de...

This manual is also suitable for:

Blueplanet 50.0tl3 basicBlueplanet 50.0tl3 mBlueplanet 50.0tl3 lBlueplanet 50.0tl3 xlBlueplanet 50.0tl3 xl-fr

Table of Contents