AC-side
Min. cable cross-section
Length of insulation to be stripped off
Tightening torque
Connection type
Ground conductor connection
Fuse protection for installation provided by customer
Fitting for AC connection
Cable diameter for cable fitting
Torque for cable fitting
Interfaces
Cable diameter for cable fitting
RS485 connection type
RS485 terminal cable cross-section
Ethernet connection type
Torque for cable fitting
Overvoltage protection
Overvoltage of DC plugs (integrated in XL version)
Overvoltage protection for AC plug (option)
Overvoltage protection for AC plug + base for a 5-core connec-
tion (option)
7.5
Connecting the device to the power grid
7.5.1
Prepare the grid connection
TN-S-System, TN-C-S-System, TT-System
↻ Connection cable with 5 strands is provided on the device.
↻ Nominal grid voltage matches the VAC nom name plate details.
1 Unfasten the cable fitting for the AC connection [ W_68].
2 Remove the outer cladding of the AC cables.
3 Push an M8 cable lug onto the PE line.
4 Remove the cover of the AC filter using the 4 screws[ T_15].
5 Unscrew the screws on the contact bridge and remove the contact bridge[
_T20].
6 Insert the AC cables through the cable fitting into the connection area.
7 Strip the AC lines [approx. 25 mm].
» Make the grid connection.
Page 20
in accordance with local installation standards
25 mm
10 Nm
screw terminal
M8
min. 100 A / max.125 A
M63
32 - 42 mm
20 Nm
11 - 17 (M25) 5 - 9.5 (M16) mm
Connector
0.25 - 1.5 mm²
RJ45
4 (M25) 1.5 (M16) Nm
Type [KACO article no.]
VAL-MS-T1/T2 1000DC-PV-ST - 2801162 [3010608] -
SPD I + II
VAL-MS 1000DC-PV-ST – 2800624 [ ] - SPD II
7P.10.8.275.0012 [3010610] – SPD I + II
7.P.20.8.275.0020 [ ] – SPD II
F-MS-T1/T2 50 ST – 2800191 – SPD I + II (Phoenix Con-
tact) [3013681]
F-MS 12 – 2817987 – SPD II - (Phoenix Contact)
[3013682]
1
4
Fig. 13: 5-core connection
1
Cover
2
Screws for contact bridge
3
Contact bridge
4
Earthing bolt
2
3
KACO blueplanet 50.0 TL3

Advertisement