B.5: Controlling All Three Inputs With One Control Module - Honeywell NOTIFIER PSE-6 Instruction Manual

Power supply expanders
Table of Contents

Advertisement

Controlling all Three Inputs with One Control Module
B.5 Controlling all Three Inputs with One Control Module
In this application, all three command inputs are being controlled by one multi-module, the XP6-C mounted inside the cabinet. Output
#1 is being used for 24 VDC aux power. Any output circuit may be configured to any input.
TB4
TB15
The following notes apply to Figure B.5.
An End-of-Line Resistor must be installed between terminals 1 and 4 for control module wiring supervision (the ELR value is
dependent on the module/FACP employed).
Either disable the unused addresses or install ELRs across unused outputs on the XP6-C.
Refer to Section 3 for instructions on setting the DIP switches.
Do not loop wires under screw terminals. Break wires to maintain proper supervision.
For a list of compatible devices, refer to the Notifier Device Compatibility Document #15378.
Refer to the SLC Wiring Manual for more information.
PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
NO NC C
NO NC C
ZNAC-PS
Class A Converter
Option Module
Figure B.5 Controlling Three Inputs with One Module
24V Aux
Power
NAC1
AUX1
NAC2
AUX2
XP6-C