Controlling all Three Inputs with One Control Module
B.5 Controlling all Three Inputs with One Control Module
In this application, all three command inputs are being controlled by one multi-module, the XP6-C mounted inside the cabinet. Output
#1 is being used for 24 VDC aux power. Any output circuit may be configured to any input.
TB4
TB15
The following notes apply to Figure B.5.
•
An End-of-Line Resistor must be installed between terminals 1 and 4 for control module wiring supervision (the ELR value is
dependent on the module/FACP employed).
•
Either disable the unused addresses or install ELRs across unused outputs on the XP6-C.
•
Refer to Section 3 for instructions on setting the DIP switches.
•
Do not loop wires under screw terminals. Break wires to maintain proper supervision.
•
For a list of compatible devices, refer to the Notifier Device Compatibility Document #15378.
•
Refer to the SLC Wiring Manual for more information.
PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
NO NC C
NO NC C
ZNAC-PS
Class A Converter
Option Module
Figure B.5 Controlling Three Inputs with One Module
24V Aux
Power
NAC1
AUX1
NAC2
AUX2
XP6-C
Application Examples
SLC
41