B.6 AC Trouble Reporting with a Conventional FACP
In this application, the PSE is being used with a conventional FACP that does not have a type-coded input zone for AC Power loss with
a delay. AC Trouble Delay on the PSE must be set to none (S1-7 ON, 8 ON). AC Fail delay timers must be set on the DACT. The DACT
must be installed in close proximity to the conventional FACP so the audible and visual signaling can be given locally at the FACP as
required by UL 864.
ELR
AC1
AC2
TB4
NO NC C
TB15
The following notes apply to Figure B.6.
Wiring from the power supply to the DACT must be in metal conduit within 20 feet of the FACP.
Refer to Section 3 for instructions on setting the DIP switches.
Do not loop wires under screw terminals. Break wires to maintain proper supervision.
An End-of-Line Resistor must be installed between terminals 1 and 4 on the input circuits that require wiring supervision. (The
ELR value is dependent on the FACP employed).
Refer to panel/DACT documentation for programming information.
42
NO NC C
PSE
Figure B.6 AC Trouble Reporting with a Conventional FACP
AC Trouble Reporting with a Conventional FACP
Channel 4
ELR
NAC
24VDC non-resettable power
+
-
+
-
+
-
+
-
B+ B-
B+
B-
B+
B-
Nonreset
ZONE 1 ZONE 2
Reset
NAC 1
NAC 2
UL 864 Listed Regulated 24 VDC
Conventional FACP
PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
Channel 1
Channel 2
Channel 3
C
NO NC
C NC NO
B+
B-
B+
B-
B+
B-
C NC NO
ZONE 3 ZONE 4
TROUBLE
ALARM
SUPV
UL 864
10th Edition
Listed DACT
ELRs