Section 1: System Overview; General; Features; Specifications - Honeywell NOTIFIER PSE-6 Instruction Manual

Power supply expanders
Table of Contents

Advertisement

The PSE-6 is a 6 amp and the PSE-10 is a 10 amp remote power supply with battery charger. Both models provide ADA compatible
strobe synchronization and a filtered 24 VDC output that can be configured to drive five (6 amp model) or seven (10 amp model) Class
B NACs (Notification Appliance Circuits). NAC circuits can be configured for Class A wiring with the optional ZNAC-PS Class A con-
verter module. NAC output circuits may be configured as 24 VDC resettable or non-resettable power outputs, or Class D door holder
outputs. The input circuits, which control the power supply operation, are triggered by the reverse polarity of a NAC or by a 12 VDC or
24 VDC power source. The PSE power supplies are compatible with 12 VDC and 24 VDC control panels.
The PSE-6E and PSE-10E offer the same features as the PSE-6 and PSE-10 respectively, but allow connection to 240 VAC. Unless oth-
erwise specified, the information in this manual applies to both the 120 VAC models and the 240 VAC models.
The PSE-6C and PSE-10C offer the same features as the PSE-6 and PSE-10 respectively, but are intended for Canadian applications and
adds an additional relay for ground fault reporting. Unless otherwise specified, the information in this manual applies to all models.
The PSE-6R and PSE-10R offer the same features as the PSE-6 and PSE-10 respectively, but come installed in a red cabinet.

1.1 General

PSE power supplies can be used as remotely mounted power supplies and battery chargers to power non-coded or coded NACs. The
Main FACP (Fire Alarm Control Panel) NAC(s) is connected to the remote power supply input circuit(s). When the command input cir-
cuit activates due to reverse polarity of the NAC from the FACP, the power supply will activate its Notification Appliance Circuits.
During the inactive or non-alarm state, the power supply supervises its NAC field wiring for short and open conditions. AC fail, battery,
charger and ground fault troubles will also be monitored by the power supply and will activate the AC Fail, Battery Fault, and Ground
Fault relay, respectively. If a NAC fault is detected, the input end-of-line will open to indicate the fault to the main panel.
If an alarm condition occurs and the NAC is activated, the supervision is disabled and the Notification Appliance Circuit is no longer
supervised (except for shorts). Supervision of other power supply faults such as low battery, overcharged battery, ground fault, and bat-
tery charger trouble will continue and will be monitored by their respective trouble relays.

1.2 Features

Self-contained in a lockable cabinet
24 VDC remote power supply
Outputs are completely power-limited (Class 2)
Two (PSE-6) or three (PSE-10) optically-isolated input/command circuits, compatible with 12 VDC and 24 VDC control panel
NACs
Five (PSE-6) or seven (PSE-10) output circuits:
– Fully filtered power
– Five or seven 24 VDC Class B NACs
– Optional ZNAC-PS Class A converter module for conversion to Class A NACs
– Alternatively, all output circuits may be configured as 24 VDC special application power outputs or Class D door holder power
outputs
– Output circuits may be configured as resettable or non-resettable
Individual NAC Power (red) and Trouble (yellow) LEDs for each output
Maximum current available:
– PSE-6: TB8-TB9 – 1A Regulated, 3A special applications; TB10-TB12 – 0.3A Regulated, 3A special applications
– PSE-10: TB8-TB11 – 1.5A Regulated, 3A special applications; TB12-TB14 – 0.3A Regulated, 3A special applications
Maximum total current available (alarm and standby):
– 6.0 amps for PSE-6 alarm; 3.0 amps standby
– 10.0 amps for PSE-10 alarm; 3.0 amps standby
Integral supervised battery charger for lead acid batteries only
Capable of charging 7.0 AH - 33.0 AH (Amp Hour) batteries (cabinet fits 7 or 18 AH batteries)
Fully supervised power supply, battery and NACs
Selectable Strobe Synchronization for NACs (System Sensor, Gentex, Wheelock, and Amseco)
Coded signal synchronization
Removable terminal blocks for field wiring capable of accepting 12 - 18 AWG wire
Selectable Ground Fault detection by switch SW1
LED trouble diagnostics and history
Power supply trouble, AC Loss, and Ground Fault (Canadian models only) Form-C relay contacts (fail-safe)
Optional delay of AC loss reporting for 0, 2, 12, or 30 hours
Mounting location for optional addressable module
Up to four PS Series units can be cascaded

1.3 Specifications

Refer to Figure 1.1 on page 10 for terminal locations.
NOTE: The PSE-6 uses the same PCB layout as the PSE-10, however some terminals will be depopulated, leaving the PSE-6 with five
output circuits and two input circuits.
8

Section 1: System Overview

PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021