B.8 Canada Two-Stage Application Using XP6-C
In this application, two outputs are being controlled by an XP6-C multi-module inside the cabinet. NAC1 from the host FACP is provid-
ing the Canada two-stage audible pattern to the PSE. NAC2 is providing master sync or a steady output, depending on its capabilities.
Additional PSE outputs can be used to connect to XP6-C modules outside the cabinet.
TB4
TB15
The following notes apply to Figure B.8.
PSE Output #1 is programmed to activate on Command Input #1 and Slave Mode (NAC Follower).
PSE Output #2 is programmed depending on host FACP capabilities:
– FACP NAC2 provides master sync: PSE output #2 activate on Command Input 2, slave mode (NAC follower)
– FACP NAC2 provides steady output: PSE output #2 activate Command Input 2, master mode (select appropriate strobe
manufacturer)
Jumpers must be installed on terminals T11, T12, T14, and T15 of the XP6-C module.
Unused control module NAC outputs need ELRs installed or must be disabled.
PSE outputs going to XP6-C need ELRs installed.
Due to the reverse-polarity supervision of the PSE outputs, the XP6-C points must have the type code, "Bell Circuit", to prevent
"Ext Power Loss" troubles.
44
T0, T1, T2
visual appliance circuits
NO NC C
NO NC C
Figure B.8 Canadian Two-Stage Wiring Using an XP6-C
T3, T4, T5
audible appliance circuits
PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
Canada Two-Stage Application Using XP6-C
Host FACP
NAC1
NAC2
SLC