Addressable Module Mounting - Honeywell NOTIFIER PSE-6 Instruction Manual

Power supply expanders
Table of Contents

Advertisement

Installation

2.3 Addressable Module Mounting

The PSE has been designed to allow the mounting of an addressable control, relay, or monitor module on the main circuit board inside
the power supply cabinet. This allows power to be fed from a PSE output circuit directly to the module, if needed, without running the
power wires outside the cabinet. Remove mounting screws from the positions indicated below and replace with standoffs (included in
hardware kit). Mount the module over the standoffs and secure with screws.
Compatible modules include the FCM-1(A), FDM-1(A), FMM-1(A), FRM-1(A), FDRM-1, XP6-C(A), XP6-R(A), XP10-M(A),
NC-100, NDM-100, NMM-100, NC-100R, and NMM-1000-R.
TB4
TB15
Figure 2.4 Mounting a Single Module in the PSE Cabinet
AC1
AC2
TB15
14
Install stacked standoffs
(0.5" + 1.093" M/F)
install 1.093" M/F
standoffs
Figure 2.5 Mounting a Multi-Module in the PSE Cabinet
NAC1
AUX1
NAC2
AUX2
Note: For instructions on mounting a multi-module and a ZNAC-PS module, refer
to the ZNAC-PS Install Sheet #LS10228-000GE-E.
The multi-module must be installed upside down when the ZNAC-PS is installed. If
the ZNAC-PS is not installed, the multi-module may be mounted in either direction.
PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
Addressable Module Mounting
NAC1
AUX1
NAC2
AUX2
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual wiring conver-
sion charts for legacy
and newer versions of
the modules.

Hide quick links: