Installation

2.5 FACP with PSE Power Supply in Slave Mode

In this application, an PSE power supply, configured as a Slave unit, is connected to a master FACP programmed for synchronized out-
put. .
TB15
The following notes apply to Figure 2.7 on page 16
1.
Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2.
Use only devices from the same manufacturer in each system.
3.
Set Output DIP Switch: position 3=ON, 4 = OFF, 5 = ON, 6 = OFF.
4.
If the FACP has a dedicated sync output connector, wire the remote sync output connector to Input #1 terminals 2 and 3.
5.
Input#1 is mapped to Slave mode output in this example, but it can programmed to another input using the DIP switches.
6.
Notification appliances cannot be installed on the FACP control circuit connecting to the PSE input circuits.

2.6 PSE Power Supply in Master Mode Connected to FACP

In this application, a master PSE power supply, set for synchronization, is connected to an FACP with non-synchronized output.
TB15
The following notes apply to Figure 2.8.
1.
Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2.
Set Output DIP switches to the desired sync protocol as described below. Refer to the Device Compatibility Document for
compatible devices.
16
PSE
Figure 2.7 Supervised Master/Slave Connections
PSE
Figure 2.8 Supervised FACP to Master Connections (non-synchronized source)
DIP Switch Position
3
4
5
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
ON
OFF
OFF
ON
ON
OFF
ELR for
FACP
NAC
ELR for
FACP
NAC
Synchronization Type
6
OFF
Slave mode (NAC follower)
OFF
Master mode - ANSI Temporal (Temporal 3)
OFF
Master mode - CO Temporal (Temporal 4)
ON
Master mode - Amseco/Potter
ON
Master mode - Gentex
ON
Master mode - System Sensor
ON
Master mode - Wheelock
ON
Master mode, Selective Silence - Amseco/Potter
ON
Master mode, Selective Silence - Gentex
PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
FACP with PSE Power Supply in Slave Mode
NAC programmed for sync
or remote sync output
FACP
NAC with no synchronization
NAC1
FACP
(also can be triggered by a
control module or relay module)