Canadian Applications

2.9 Canadian Applications
Installation shall be in accordance with ULC S524. Wiring methods shall be in accordance with CSA C22.1, Safety Standard for Electri-
cal Installations, Canadian Electrical Code, Part I, Section 32.
NOTE: Mass Notification is not for use in Canadian applications.
Canadian applications, per ULC, require the following:
Connect the AC ground wire to the Ground Stud located at the top left of the backbox as shown below. Connect the incoming earth
ground wire to supplied cable #71073 with a wire nut. Position the ring terminal end over the grounding stud. Secure with one of
the keps nuts. Place the ring terminal from the other supplied ground cable #71073 over the ground stud and secure with the second
keps nut. Wire the ground cable to the middle position of TB4. Ensure that the ground for incoming AC mains is the first wire
installed, closest to the backbox. This connection is vital in reducing the panel's susceptibility to transients generated by lightning
and electrostatic discharge. Apply AC power to the panel only after the system is completely installed and visually checked. Note
that AC power must be applied to the panel before installing the battery interconnect cable.
Grounding Cable
keps nut
Refer to Section 5.1 for instructions to meet ULC requirements for trouble monitoring of each zone.
PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
#71073
grounding stud
keps nut
Figure 2.13 Earth Ground Connection
Installation
19