5.1 Controlling Four NAC Circuits from a Single Source

In this application, all four NACs (Notification Appliance Circuits) are controlled by a single input from a FACP (Fire Alarm Control
Panel) as illustrated in Figure 5.1. The FACP could be replaced by a supervised addressable control module associated with a fire alarm
control panel.
If the Programming DIP Switches are set as shown below, all four NACs will follow (Pass-through/Slave) the signal from the FACP.
SW1-8
OFF
All four NAC outputs will follow FACP output. FACP output can be steady on, coded, temporal, sync, etc.
LEDs
Notes for Figure 5.1:
1.
When the power supply is in normal/standby state, a trouble will result in an open circuit condition on the FACP's NAC circuit
(monitored by End-of-Line Resistor across TB3). The HPFF's alarm input circuit will always remain closed in the alarm state.
Therefore, the Trouble contacts at TB2 need to be used to report troubles to the FACP during an alarm. See Section 4.1, "Supervised
Functions and Field Wiring".
2.
The FACP's NAC circuit can be steady on, coded, temporal, Sync, etc.
3.
The value of the ELR (End-of-Line Resistor) across TB3 terminals SIGNAL 2 +OUT & -OUT depends on the FACP used.
4.
For a list of compatible devices, refer to the HPP Device Compatibility Document.
5.
The same gauge wire must be used if two conductors are connected to the same terminal of any terminal block.
6.
Do not complete a continuous circuit around the screw terminal. There must be two separate wires on either side of the screw at the
terminal block. "T-tapping" is absolutely NOT ALLOWED.
HPFF8(E)/HPFF8CM(E) NAC Expander — P/N 53499:B4 10/1/2018

Section 5: Applications

SW1-7
SW1-6
N/A
OFF
TB2
J1
TB1
TB4
A+
BATT+ BATT–
A–
1L1
1L2
Figure 5.1 Controlling Four NAC Circuits from a Single Source
SW1-5
SW1-4
OFF
OFF
SW2
Ref +
Ref -
In #1 +
In #1 -
Out #1 +
Out #1 -
In #2 +
In #2 -
Out #2 +
Out #2 -
J2
3L1
3L2
2L1
2L2
4L1
4L2
SW1-3
SW1-2
OFF
OFF
TB3
Ref
-
NAC Output
from FACP
ELR
Alarm Polarity
Shown
SW1-1
OFF
+
35