Connecting to an External Charger

3.
Use only devices from the same manufacturer in each zone or field of view.
4.
Input#1 is mapped to Master mode output in this example, but it can programmed to another input using the DIP switches.
5.
Notification appliances cannot be installed on the FACP control circuit connecting to the PSE input circuits.
2.7 Connecting to an External Charger
The PSE Power Supply can be connected to an external charger to charge systems requiring over 33AH batteries. Ensure all power has
been disconnected before wiring. Observe polarity when making connections. Wiring must be in conduit within 20 feet (6.096m) in the
same room.
2.7.1 CHG-120
1.
Set S1 position 4 on the PSE Power Supply to the OFF position to disable the onboard battery charger.
2.
Connect the battery cables between TB15 (+ and –) on the PSE and the CHG-120 charger output circuit (TB2: Out 1+ and Out 1–)
as shown in Figure 2.9. Be certain to observe polarity.
3.
Connect the batteries to the charger.
4.
Connect the battery interconnect cable only after AC power is applied and batteries are connected. Refer to the CHG-120 Manual
for more information.
Note: If batteries are
disconnected at the
CHG-120 terminals,
battery supervision will
be managed by the
CHG-120
2.7.2 CHG-75
1.
Set S1 position 4 on the PSE Power Supply to the OFF position to disable the onboard battery charger.
2.
Connect the battery cables between TB15 (+ and –) on the PSE and the CHG-75 charger output circuit (TB2: Out+ and Out–) as
shown in Figure 2.10. Be certain to observe polarity.
3.
Connect the batteries to the charger.
4.
Connect the battery interconnect cable only after AC power is applied and batteries are connected. Refer to the CHG-75 Manual for
more information.
JP1
CUT FOR
240VAC
F1
TB1
PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
ON
OFF
ON
ON
ON
ON
TB1
CHG-120
Charger
TB2
Battery interconnect cable
+
12V battery
Figure 2.9 Connecting the Power Supply to a CHG-120 Charger
CHG-75
TENS
0
1 1
5 7
10
Charger
8
14
1
12
13
6
15
2
9
4 3
1 1
0
5 7
10
8
14
1
12
13
6
15
2
9
4 3
ONES
Battery interconnect cable
-
-
+
12V
12V
battery
battery
Figure 2.10 Connecting the Power Supply to a CHG-75 Charger
ON
Master mode, Selective Silence - System Sensor
ON
Master mode, Selective Silence - Wheelock
+
+
+
+
12V battery
J4
AM-1
TB2
+
-
TB2
+
-
ADDRESS
SW1
ON
OFF
TB3
TB4
J1 J2 J3
A- B- A+ B+
NC NO C
+
TB4
NO NC C
NO NC C
PS Series Power Supply
Set S1 position 4 to
the OFF position to
disable charger
TB15
PS Series Power Supply
Set S1 position 4 to
the OFF position to
disable charger
-
+
Installation