B.1 Controlling NACs For Selective Silence Operation Using a Control Module
In this application, the power supply has been set as a master with synchronized outputs and selective silence (see DIP switch settings
and Selective Silence Operation information in Section 3). This application requires Input #1 to be controlled by the FACP. Input #2 is
required for controlling selective silence via a control/relay module, programmed as an alarm output and a silenceable point. Only Mass
Notification, Fire, or combo Mass Notification/Fire NACs are allowed in this configuration. The control module can be powered by one
of the PSE output circuits, configured as aux power (24VDC).
TB4
Control Module*
*If the SLC device does not match
the one in this figure, refer to the
SLC manual wiring conversion
charts for legacy and newer ver-
sions of the modules.
TB15
The following notes apply to Figure B.1.
When the PSE power supply is in an inactive state (FACP NAC not active), a trouble on the NAC circuit will result in an open circuit
condition on the FACP (monitored by End-of-Line Resistor across TB5, Terminals 1 and 4). As an alternative, the trouble contacts at
TB1 of the power supply can also be used for limited trouble monitoring excluding Selective Silence output faults. Refer to Section 5 for
more information.
Refer to Section 3 for instructions on setting the DIP switches.
Selective Silence output faults are only reported via Command Input #1 (not Command Input #2).
Wire NACs as shown on page 13.
Do not loop wires under screw terminals. Break wires to maintain proper supervision.
An End-of-Line Resistor must be installed across all input circuits, Terminals 1 and 4, for control module wiring supervision (the
ELR value is dependent on the module/FACP employed).
For a list of compatible devices, refer to the Notifier Device Compatibility Document #15378.
Refer to the SLC Wiring Manual for more information.
PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021

Appendix B: Application Examples

NAC Output Circuits
NO NC C
NO NC C
Figure B.1 Controlling Multiple Outputs with One Input