Honeywell NOTIFIER PSE-6 Instruction Manual page 30

Power supply expanders
Table of Contents

Advertisement

LED Indicators
Output Circuit Status LEDs (red)
Output inactive
Output active
Output Circuit Trouble LEDs (yellow)
No Fault
Fault Condition (Normal/Standby Mode):
Wire Supervision
Class A or B Open circuit
1 short blink (250ms)
Fault Condition (Normal/Standby Mode):
Wire Supervision
Class A or B Short Circuit
2 short blinks (250ms)
Fault Condition:
Aux Power Supervision
Class A Open circuit
(ZNAC-PS Circuit #1 and #2 only)
3 short blinks (250ms)
Fault Condition:
Power limit condition (individual ckt overload)
4 short blinks per individual circuit (250ms)
Fault Condition:
Power limit condition (panel overload)
4 short blinks on all output circuits (250ms)
Operating Mode Fault:
Power Supply not in Normal Operating mode
1 short blink from right to left across all output
circuits.
Set positions 9 and 10 on S1 to the ON
position.
30
LED is OFF
LED is ON constant
LED is OFF
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
Repeating LED blink pattern (non-diagnostic mode)
250ms 250ms 250ms 250ms 250ms 250ms 250ms 250ms
PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
pause
1000ms
pause
1000ms
pause
1000ms
pause
1000ms
pause
1000ms