Type 8692/8693
CANopen
3.29 0x2C02
Only available for devices with process controller function
sub name
2
FTfgPV
3
DBDp
4
KP
5
TN
6
TV
7
X_0
8
mPCONsetp
9
mPCONinp
0xA
mPcoInitMode
0xF
PT100offset_user
Bedienungsanleitung Software
PCONTROL
Description
Predefined filter setting Values for the process value input
0: Filter 0 (10 Hz)
1: Filter 1 (5 Hz)
2: Filter 2 (2 Hz)
3: Filter 3 (1 Hz)
4: Filter 4 (0,5 Hz)
5: Filter 5 (0,2 Hz)
6: Filter 6 (0,1 Hz)
7: Filter 7 (0,07 Hz)
8: Filter 8 (0,05 Hz)
9: Filter 9 (0,03 Hz)
Deadband of process controller in % (Scaled with PCOmin
and PCOmax)
Proportional gain of the process controller
Integral action time of the process controller in s
Derivative action time of the process controller in s
Operating point of the process controller, position in %
0:SP source is SP_Manual (2C01subC)
1: SP source is extern (fielbus or analog input)
Selecting the type of analog input for ProcessValue of the
process controller
0:FMR (only if FMR device)
1:4-20 mA
2:Ferquency
3:PT100
4:BUS (BueS/Fieldbus)
P.CO initialization mode
0: Standard
1: Bumpless
2: Zero-Init
PT100 calibration offset
X
RW
X
RW
X
RW
X
RW
X
RW
X
RW
X
RW
X
RW
X
RW
X
RW
Seite 18 / 28