GE Multilin 350 Series Instruction Manual page 114

Feeder protection system
Hide thumbs Also See for Multilin 350 Series:
Table of Contents

Advertisement

QUICK SETUP SETTINGS
5–4
Courtesy of NationalSwitchgear.com
GND TOC FUNCTION
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
GND TOC PICKUP
Range: 0.04 to 20 x CT
Default: 1.00 x CT
GND TOC CURVE
Range: ANSI Extremely/Very/Moderately/Normally Inverse; Definite
Time; IEC Curve A/B/C /Short Inverse; IAC Extreme/Very/Inverse/Short
Inverse; User Curve, FlexCurve™ A/B (programmable curves)
Default: Extremely Inverse
GND TOC TDM
Range: 0.50 to 20.00
Default: 1.00
SENS GND TOC FUNCTION [WHEN SPECIFICALLY ORDERED]
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
SENS GND TOC PICKUP
Range: 0.005 to 3.000 x CT
Default: 1.000 x CT
SENS GND TOC CURVE
Range: ANSI Extremely/Very/Moderately/Normally Inverse; Definite
Time; IEC Curve A/B/C /Short Inverse; IAC Extreme/Very/Inverse/Short
Inverse; User Curve, FlexCurve™ A/B (programmable curves)
Default: Extremely Inverse
SENS GND TOC TDM
Range: 0.50 to 20.00
Default: 1.0
NTRL TOC FUNCTION
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
NTRL TOC PICKUP
Range: 0.04 to 20.00 x CT
Default: 1.00 x CT
NTRL TOC CURVE
Range: ANSI Extremely/Very/Moderately/Normally Inverse, Definite
Time, IEC Curve A/B/C and Short, IAC Extreme/Very/Inverse/Short, User
Curve, FlexCurve™ A/B (programmable curves)
Default: Extremely Inverse
NTRL TOC TDM
Range: 0.50 to 20.00
Default: 1.00
CHAPTER 5: QUICK SETUP - FRONT CONTROL PANEL
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL