5.TECHNICAL SPECIFICATIONS

Supply
Maximum consumption
Controller operating temperature
Operating humidity
Type action
Pollution degree
Software class
Control pressure
Pressure resolution
Control temperature
Temperature resolution
Analog inputs
Voltage output for pressure sensors
Digital inputs
Analog outputs
Digital outputs
USB Interface
RS-485 communication interface
Product dimensions (LxAxP)

6.ELECTRICAL PRECAUTIONS

BEFORE INSTALLING THE CONTROLLER, WE RECOMMEND THAT THE FULL READING OF THE INSTRUCTION MANUAL BE DONE, IN
ORDER TO AVOID POSSIBLE DAMAGE TO THE PRODUCT.
PRECAUTION WHEN INSTALLING THE PRODUCT:
-Before performing any procedure on this instrument, disconnect it from the power supply;
-Certify that the instrument has adequate ventilation, avoiding installation on panels that contain devices that may cause it to operate outside the
specified temperature limits;
-Install the product away from sources that may generate electromagnetic disturbances, such as: motors, contactors, relays, solenoid valves, etc.
AUTHORIZED SERVICE:
-Installation or maintenance of the product must be performed only by qualified professionals.
ACCESSORIES:
-Use only Full Gauge Controls original accessories;
-In case of doubt, contact technical support.
BEING IN CONSTANT DEVELOPMENT, FULL GAUGE CONTROLS RESERVES THE RIGHT TO CHANGE ANY INFORMATION IN THE MANUAL
AT ANY TIME, WITHOUT PRIOR NOTICE.
6
S1 to S6: Configurable between pressure sensor (4 to 20mA / SB69) or
temperature sensor (SB19, SB41, SB59, SB70);
Voltage output +12V: 12Vdc, Idcmax= 120mA;
Hi1 to Hi3: Isolated digital inputs, with maximum voltage equal to the supply
O1, 05 and O6: relay output (SPST) NA, 5(3)A/250Vac;
O2, O3, and O4: output with solid state relay (SSR) 1A/24 - 240Vac
Compatible with the USB 2.0 Full-Speed Module (USBFS) standard;
Data format for FAT32 pendrive / Maximum size of 32GB pendrive
70,0 x 135,7 x 61,7 mm (2,76" x 5,34" x 2,43")
24Vac 50/60Hz or 24Vdc 10%
10 to 90% UR (without condensation)
0.1 psi / 0.1 bar
-14,7 to 850psi / -1,0 to 58,7 bar
-50 to 200°C / -58 to 392°F
0.1°C / 0.1 °F across all range
I1 to I5: dry contact type digital inputs.
A1000000000000000000000
= 0-10Vdc (max. 10mA)
A2000000000000000000000
RS485-1: Not insulated
RS485-2: Insulated
EXP: Communication with expansion modules
±
500mA ac/dc
0 to 50°C
Type 1.B
II
Class A
voltage (24V)

Advertisement