Full Gauge Controls MT-514e Manual

Full Gauge Controls MT-514e Manual

Digital controller for heating or cooling with defrost and configurable alarm output

Advertisement

Quick Links

Have this manual in the palm of
your hand by FG Finder application.
BEFORE INSTALLING THE CONTROLLER, WE RECOMMEND READING THROUGH THE
ENTIRE INSTRUCTION MANUAL IN ORDER TO AVOID POSSIBLE DAMAGE TO THE
PRODUCT.
PRECAUTIONS WHEN INSTALLING THE PRODUCT:
Before performing any procedure on this instrument, disconnect it from the mains;
Ensure that the instrument has adequate ventilation and avoid installation in panels containing
devices that may cause it to operate outside the specified temperature limits;
Install the product away from sources that may generate electromagnetic disturbances such as:
motors, contactors, relays, solenoid valves, etc;
AUTHORIZED SERVICE:
The installation or maintenance of the product must be performed by qualified professionals only;
ACCESSORIES:
Only use original Full Gauge Controls accessories.
If you have any questions, please contact technical support.
DUE TO YOUR CONSTANT EVOLUTION, THE FULL GAUGE CONTROLS RESERVES THE RIGHT TO
CHANGE THE INFORMATION CONTAINED IN THIS MANUAL AT ANY TIME WITHOUT NOTICE.
1. DESCRIPTION
It is a temperature-based controller designed for cooling or heating applications. It is loaded with one
temperature sensor and two outputs of control, including a SPDT contact that can be used for alarm or
defrost purposes. Defrost can be electric or hot gas. The controller offers a built-in buzzer and a digital
input which can be configured for door alarm or power outage alarm, or detection of both events through
the single digital input. Two configurable preset options is available for quick parameter change. Preset
include variables such as temperature setpoint, differential and cooling time (interval between
defrosts). Other salient features include internal buzzer, IP65 frontal, min-max temperature record,
temperature sensor response-time control, tamper-proof function and control functions shutdown.
Product conforming to UL Inc. (United States and Canada) and NSF
2. APPLICATION
• Vaccine refrigerators
• Refrigerated counters
• Freezer rooms
• Hot counters
• Greenhouses

3. TECHNICAL SPECIFICATIONS

Power supply
Control temperature
Operating temperature
Load current (outputs)
Operating humidity
Dimensions (mm)
Dimensions of the clipping for fixing
of the instrument
(*) This instrument measures and controls temperatures of up to 200°C/392°F, using the silicone sensor cable SB59
(sold separately).
Note: The sensor cable lenght can be increased by the user up to 200 meters using PP 2 x 24 AWG cable.

4. INDICATIONS AND KEYS

Defrost indication LED
Heating indication LED
Cooling indication LED
Quick Access
Menu Key (Flatec)
Set key
e
MT-514

5. INSTALLATION - ASSEMBLING AND ELECTRICAL CONNECTIONS

(Side View)
MT-514
DIGITAL CONTROLLER FOR HEATING OR COOLING
WITH DEFROST AND CONFIGURABLE
ALARM OUTPUT
Audible
Defrost
Function
Control functions
Alarm
blocking
WARNING
(United States)
.
MT-514 E: 115 or 230 Vac ±10%(50/60 Hz)
MT-514 EL: 12 or 24 Vac/dc +10%
-50 to 105ºC (-58 to 221°F)*
0 to 50 ºC / 32 to 122°F
OUT1: 16(12)A 250Vac 2HP
OUT2: 10A / 240Vac 1/4HP
10 to 90%RH (without condensation)
76 x 34 x 77 mm (WxHxD)
71 ± 0,5 x 29 ± 0,5 mm (see item 5)
Alarm indication LED
Functions lock indication LED
Temperature unit indication LED
71
± 0,5
mm
Dimension of the clipping
for fixing of the
instrument in panel
Panel
Panel (Front View)
e
IP 65
FRONT
Serial
Protection
shutdown
Programming
level
ATTENTION
FOR INSTALLATIONS WHERE A SEALING IS REQUIRED
TO AVOID LIQUID CONTACT, THE CUT FOR THE
CONTROLLER MUST BE OF 70,5X29mm MAXIMUM. THE
SIDE LOCKS MUST BE FIXED SO IT PRESSES THE
RUBBER SEALING AVOIDING INFILTRATION BETWEEN
THE CUT AND THE CONTROLLER.
Connection
115 Vac
Connection
230 Vac
Connection
12 Vac/dc
Connection
24 Vac/dc

6. OPERATIONS

6.1. Quick Access Menu Map
To access or browse in the quick access menu, use the
being displayed by the controller. Each touch displays the next function of the list; for confirming, use
/
the
key (quick touch). For further details, refer to chapter 6.3.
DEFROST (ON/OFF)
;
e
MT-514
FUNCTIONS LOCKDOWN
;
e
MT-514
CONTROL FUNCTIONS
(ON/OFF)
;
e
Increase key
MT-514
ADJUSTING DESIRED
TEMPERATURE
Decrease key
(SETPOINT)
;
e
MT-514
6.2 Quick access keys map
When controller is on temperature display mode, the following keys can be used as a shortcut for the
following functions:
/ <
Hold down for 2 seconds: Setpoint adjustment.
Quick touch: Current process display.
<
Hold down for 2 seconds: Inhibit audible alarm (buzzer).
<
Quick touch: Maximum and minimum temperature display.
e
e
M T- 51 4
M T- 51 4
IMPORTANT
THE USE OF APPROPRIATE TOOLS IS ESSENTIAL TO AVOID
DAMAGE IN THE CONNECTION AT INSTRUMENT TERMINALS:
SCREWDRIVER SLOT 3/32''(2.4mm) FOR ADJUSTMENTS IN THE
SIGNAL TERMINALS;
SCREWDRIVER PHILLIPS #1 FOR ADJUSTMENTS IN THE POWER
TERMINALS;
POWER
5 6 7 8
NC
SUPPLY
NO
9
10 11 12 13 14 15 16 17
1
2 3 4
D1
SENSOR
/
POWER
5 6 7 8
NC
SUPPLY
NO
9
10 11 12 13 14 15 16 17
1
2 3 4
D1
SENSOR
/
POWER
5 6 7 8
NC
SUPPLY
NO
9
10 11 12 13 14 15 16 17
1
2 3 4
D1
SENSOR
/
12 Vac/dc
POWER
5 6 7 8
NC
SUPPLY
NO
9
10 11 12 13 14 15 16 17
1
2 3 4
D1
SENSOR
/
24 Vac/dc
;
key (quick touch) while the temperature is
MIN. AND MAX.
TEMPERATURE RECORD
;
e
MT-514
evolution
COMPONENT
E251415
REFR
HEAT
115 Vac
Loads supply
REFR
HEAT
230 Vac
Loads supply
REFR
HEAT
Loads supply
REFR
HEAT
Loads supply
EXIT FUNCTION
;
e
MT-514
FUNCTION SELECTION
;
e
MT-514
VISUALIZATION OF
PROCESSES
;
e
MT-514
ERASE MIN. AND MAX.
VALUES
;
e
MT-514

Advertisement

loading

Summary of Contents for Full Gauge Controls MT-514e

  • Page 1 5 6 7 8 HEAT SUPPLY DUE TO YOUR CONSTANT EVOLUTION, THE FULL GAUGE CONTROLS RESERVES THE RIGHT TO 230 Vac 10 11 12 13 14 15 16 17 CHANGE THE INFORMATION CONTAINED IN THIS MANUAL AT ANY TIME WITHOUT NOTICE.
  • Page 2 Note 1: The minimum and maximum temperature records shall only be performed after the elapsing of < Hold down for 4 seconds: Carries out manual defrost. the alarm inhibition time when energizing the controller and after the delay in the instrument energizing [,F27] + [,F19].
  • Page 3 F03 - Using Presets: F20 - Compressor status with the sensor damaged: Allows configuration of the controller so as whether or not to use the presets: If the sensor is in short-circuited, off or out of the measure range, the compressor assumes the set status [no,,]- No: If configured this way, the instrument will not use the preset values in the control routines.
  • Page 4 Extension Frame alarm. The Full Gauge Controls extension frame allows the installation of Evolution / Ri line with measures 76x34x77 mm (dimensions of the clipping for fixing in the extension frame is 71x29mm) in varied F33 - Operating mode of the digital filter: situations, since it eliminates precision cut to embed the instrument.
  • Page 5 If in doubt, please contact Full Gauge Controls. Products manufactured by Full Gauge Controls, as of May 2005, have a two (02) year warranty, as of the date of the consigned sale, as stated on the invoice. They are guaranteed against manufacturing defects that make them unsuitable or inadequate for their intended use.