Beko METPOINT BDL Instructions For Installation And Operation Manual page 59

Graphic display-recorder
Table of Contents

Advertisement

Fifth step: define the register
Main menu  Settings  Sensor settings  A1 Va  use
Sixth step: enter the Modbus parameters
The following parameters can be retrieved via the corresponding registers:
Register
Designation
Va
Temperature
Vb
Rel. humidity
Vc
Dew-/frostpoint
Vd
Dew point
METPOINT® BDL
The definition of further registers is imple-
mented in the same manner.
The settings of the reg./data format are the
same for all registers.
The entry of the Modbus parameters is im-
plemented via the white buttons (1) – (4).
Address of register Reg. format
1216
[HR] R4
1152
[HR] R4
1536
[HR] R4
1472
[HR] R4
Operation BDL
Unit
Scal.
°C
No scal.
% rH
No scal.
°Ctd
No scal.
°Ctd
No scal.
59