oventrop Aktor M ST L Modbus Operating Instructions Manual page 18

Electromotive actuator
Table of Contents

Advertisement

Appendix
318
uint16
Operating status /
Error
319
uint16
Current flushing timer
320
uint16
Current valve an-
ti-blocking timer
321
uint32
Operating time
323
uint32
Travel counter
400
uint16
Nominal value volume
flow (control signal)
401
uint16
Actual value volume
flow
402
uint16
Current calculated
volume flow
403
int16
Room temperature
404
int16
Flow temperature
405
int16
Return temperature
406
int16
Differential temperature r
407
uint16
Leakage warning
408
uint16
Digital contact 1
409
uint16
Digital contact 2
410
uint16
Current calculated
thermal output
411
uint16
Energy since 0 a.m.
412
uint16
Energy last 24h
413
uint16
Change-over status
414
uint16
Current maximum vol-
ume flow
415
uint16
Initial value PI controller r
418
uint16
Nominal position
419
uint16
Actual position
420
uint16
Learned total travel
424
int16
Sensor input P1
425
int16
Sensor input P2
426
uint16
Y output P2
18
r
0x0000: Normal operation, no message
0x0001: Disturbance internal memory
0x0002: Disturbance internal AD conversion
0x0004: Disturbance valve adaptation
0x0008: Disturbance internal motor function
0x0010: P1 range excess
0x0020: P2 range excess
0x0040: Disturbance calculation/control functions
0x0080: Permanent blocking of the valve
0x0100: Command execution test run/adaptation active
r
Minutes remaining until flushing
r
Minutes remaining until valve anti-blocking
r
Seconds
r
mm
r/w
0..10000 = 0..100%
r
0..10000 = 0..100%
r
l/h
r(w)
°C*10 (write protected in case of assigned source P1 or P2)
r/(w)
Current flow temperature in °C*10 (write protected in case
of assigned source P1 or P2)
r/(w)
Current return temperature in °C*10 (write protected in case
of assigned source P1 or P2)
Calculated difference from flow/return temperature register
in K*10
r
0: No warning; 1: Leakage detected (valve closed for more
than 6h, differential temperature exceeding 8 K)
r
0/1
r
0/1
r
kW*10 (display in cooling and heating mode without signs.)
r
kWh*10
r
kWh*10
r
0: Shut-off ; 1: Heating ; 2: Cooling
r
Current value in l/h
0..100%
r
mm*10
r
mm*10
r
mm*10
r
V*100,°C*10; 0/1
r
V*100,°C*10; 0/1
r/w
Voltage value 0..1000 for output signal 0..10V (for configura-
tion I/O type P2: 8: Y output 0..10V)
„Aktor M ST L Modbus"
101274584-V01.11.2019

Advertisement

Table of Contents
loading

Table of Contents