oventrop Aktor M ST L Modbus Operating Instructions Manual page 17

Electromotive actuator
Table of Contents

Advertisement

„Aktor M ST L Modbus"
134
uint16
Emergency position
135
uint16
Flushing timer
136
uint16
Valve anti-blocking
timer
138
uint16
Command
200
uint16
Operating mode
201
uint16
Change-over mode
300
uint16
Nominal value room
temperature
301
uint16
Nominal value thermal
Power consumption
302
uint16
Nominal value return
temperature
303
uint16
Nominal value differen-
tial temperature
307
uint16
PI_TNOMINAL
308
uint16
PI_TACTUAl
310
uint16
PI_XP
311
uint16
PI_TN
312
uint16
Travel limit in % min
313
uint16
Travel limit in % max
314
uint16
Thermal output limit
315
uint16
Return temperature
limit
316
uint16
Differential temperature
limit
101274584-V01.11.2019
r/w
0..10000 = 0..100.0%
r/w
Value in minutes, 0: = inactive (smallest interval 60 minutes)
r/w
Value in hours, 0: = inactive (smallest interval 24 hours)
r/w
0: Normal operation
1: Valve adaptation / initialisation run 2: Test run
3: Sync
4: Error reset
5: Acceptance of the transmission parameters (Baud rate,
parity & stop bits)
r/w
0: Steuerung über Sollwert
1: Auf
2: Zu
3: MinPos
5: MaxPos
6: Temperature control according to register "room temper-
ature"
7: Output control according to register "thermal output"
8: Temperature control according to register "return temper-
ature"
9: Temperature control according to register "differential
temperature"
r/w
0: Shut-off
1: Heating
2: Cooling
3: Automatic according to flow temperature
r/w
°C*10
r/w
kW*10
r/w
°C*10
r/w
°C*10
r
Current nominal value for PI controller
r
Actual value for PI controller, source see setting "operating
mode"
r/w
Proportional value Xp*10
r/w
Reset time Tn in seconds
r/w
0..10000 = 0..100.0%
r/w
0..10000 = 0..100.0%
r/w
kW*10; 0 = inaktiv
r/w
°C*10; 0 = inactive
r/w
°C*10; 0 = inactive (difference between supply and return)
Appendix
17