„Aktor M ST L Modbus"
10. Appendix
10.1 Modbus topology
MASTER
Illust. 7: Modbus topology
NOTICE
Disturbances during signal transmission in the bus system
If the Modbus is not terminated correctly, communication disturbances between the components may
occur.
f Install a terminal resistance (120 Ohm) at the beginning and the end of the Modbus between the
data lines D+ and D-.
10.2 Data point list
Register
Data
Name
address
type
0
uint16
Type
1
uint16
FW version
2
uint16
HW identifier
3
uint16
SerNum1
4
uint16
SerNum2
5
uint16
SerNum3
101
uint16
Time hour
102
uint16
Time minute
105
uint16
RS485 Baud rate
106
uint16
RS485 Stop bits
107
uint16
RS485 Parity
110
uint16
Selection of the current
valve characteristic line
113
uint16
Maximum volume flow
of the selected valve
101274584-V01.11.2019
00
AKTOR
1 2 3 4
R/W
r
r
r
r
r
r
r/w
r/w
r/w
r/w
r/w
r/w
r
01
AKTOR
1 2 3 4
Values
1: Aktor
e.g. 123 = version 1.23
e.g. 0x00F1
0-65535
0-65535
0-65535
0-23 to be set manually (no battery buffered RTC)
0-59 to be set manually (no battery buffered RTC)
0: default (38400,N,8,2) ; 1: 9.600 ; 2: 19.200 ; 3: 38.400 ; 4:
57.600 ;
5: 115.200
1, 2
0: none ; 1: even ; 2: odd
0: linear
1: Cocon QTR DN40 1500-7500 l/h
2: Cocon QTR DN50 IG 3500-14000 l/h
3: Cocon QTR DN40 AG 1500-7500 l/h
4: Cocon QTR DN50 AG 3500-10000 l/h
5: Cocon QFC DN40 1500-7500 l/h
6: Cocon QFC DN50 2000-8000 l/h
In l/h, is set when selecting the valve characteristic line
02
AKTOR
1 2 3 4
Appendix
n
15