Electrical Connections; Configuration Of The Dip Switches - oventrop Aktor M ST L Modbus Operating Instructions Manual

Electromotive actuator
Table of Contents

Advertisement

„Aktor M ST L Modbus"
5.2

Electrical connections

4
3
2
1
Illust. 3: Electrical connections, DIP switches and
status LED
(1)
Red
24 V AC/DC
(RD)
(2)
Black
0 V AC/DC
(BK)
(3)
Yellow
D+
(YE)
(4)
Green
D-
(GN)
(7)
White
P1
(WH)
(8)
Violet
GND
(VT)
(9)
Grey
P2
(GY)
(10) Pink
GND
(PK)
(11) DIP switch panel
(12) Status LED
101274584-V01.11.2019
Data line
Data line
Universal input 1
Universal input 1 earth
Universal input 2
Universal input 2 earth
11
RD BK
24 V AC/DC
0 V AC/DC
12
D+
D-
Illust. 4: Connection diagram
7
NOTICE
8
Short circuit due to dripping water
f Do not feed the cable in from the top.
9
1. Remove the casing cover.
10
2. Connect the data lines for the Modbus and, if
required, the lines for the universal inputs according
to the assignment in Illust. 4 on page 11 an.
3. Connect the lines for the power supply according to
the assignment in Illust. 4 on page 11.
4. Connect the power supply.
Z The LED will flash green quickly.
5.3

Configuration of the DIP switches

Address 00 is always occupied by the Modbus
master.
The terminal resistance (120 Ohm) between the
two data lines (D+ and D-) is inactivated ("OFF")
or activated ("ON") via DIP switch 8.
f Make sure that both ends of the bus are
terminated by a terminal resistance.
1. Remove the casing cover.
2. Configure the DIP switches according to the desired
Modbus address.
M
1
2 3 4
7 8
YE
WH
VT
GY PK
GN
Installation
9 10
GND
P2
GND
P1
11

Advertisement

Table of Contents
loading