Nibe AirSite GreenMaster-HP 12 Series Installer Manual page 41

Exhaust air heat pump for properties
Table of Contents

Advertisement

choose another file
update firmware7.1
Select "choose another file" if you do not want to use
the suggested software. When you scroll through the
files, information about the marked software is shown
in a fact box just as before. When you have selected a
file with the OK button you will return to the previous
page (menu 7.1) where you can choose to start the up-
date.
Menu 7.2 - logging
activated
interval
Setting range: 1 s – 60 min
Factory setting range: 5 s
Here you can choose how current measurement values
from GreenMaster-HP should be saved onto a log file on
the USB memory.
1. Set the desired interval between loggings.
2. Tick "activated".
3. The present values from GreenMaster-HP are saved
in a file in the USB memory at the set interval until
"activated" is unticked.
Caution
Untick "activated" before removing the USB
memory.
Logging floor drying
Here you can save a floor drying log on the USB memory
and in this way see when the concrete slab reached the
correct temperature.
Make sure that "floor drying function" is activated in
menu 5.9.
Select "logging floor drying activated".
GreenMaster-HP
logging7.2
min
A log file is now created, where the temperature and
the immersion heater output can be read off. Logging
continues until "logging floor drying activated" is
deselected or until "floor drying function" is stopped.
Caution
Deselect "logging floor drying activated" before
you remove the USB memory.
Menu 7.3 - manage settings
manage settings 7.3
save settings
recover settings
Here you can manage (save as or retrieve from) all the
menu settings (user and service menus) in GreenMaster-
HP with a USB memory.
Via "save settings" you save the menu settings to the
USB memory in order to restore them later or to copy
the settings to another GreenMaster-HP.
Caution
When you save the menu settings to the USB
memory you replace any previously saved set-
tings on the USB memory.
Via "recover settings" you reset all menu settings from
the USB memory.
Caution
Reset of the menu settings from the USB
memory cannot be undone.
Chapter 8 |
Service and maintenance