10. Lift off the heat exchanger.
11. If the cooling module does not need to be removed,
skip this step: Disconnect the cables and connectors
that are fitted in the distribution box in front of the
cooling module. Then disassemble the distribution
box in front of the cooling module by loosening the
metal spacers to which the distribution box is at-
tached. NOTE! Also loosen the two earth cables that
are run out of the distribution box.
GreenMaster-HP
6x
12. Disconnect all the connections connecting the centre
module with the two outer modules. Also, discon-
nect the PVC pipe for the waste water.
13. Unscrew the wall bracket securing the expansion
vessel to the stay.
14. Remove the switch on the level vessel.
15. Undo the screw joint securing the level vessel to the
stay.
TIP
Disconnect and pull out the cooling mod-
ules according to the instructions on page
39 before dismantling the lower sections
for easier handling.
16. Lift off the right-hand module and dismantle the
condensation pipe in the cooling module that runs
down to the floor.
Chapter 2 |
Delivery and handling
11