Nibe AirSite GreenMaster-HP 12 Series Installer Manual page 28

Exhaust air heat pump for properties
Table of Contents

Advertisement

is set with the number of steps selected. The value is
adjustable between -10 and +10. External adjustment
of climate systems 2 to 8 requires accessories.
climate system 1 to 8
The value for the change is set in menu 1.9.2, "extern-
al adjustment".
activation of one of four fan speeds.
(Can be selected if ventilation accessory is activated.)
The following five options are available:
1–4 is normally open (NO)
1 is normally closed (NC)
The fan speed is activated during the time the switch
is closed. Normal speed is resumed when the switch
is opened again.
SG ready
Caution
This function can only be used in mains net-
works that support the "SG Ready" standard.
"SG Ready" requires two AUX inputs.
"SG Ready" is a smart form of tariff control, which al-
lows your electricity supplier to affect the indoor, hot
water and/or pool temperatures (if applicable) or
simply block the additional heat and/or compressor
in GreenMaster-HP at certain times of the day (can be
selected in menu 4.1.5 after the function is activated).
Activate the function by connecting potential-free
switch functions to two inputs selected in menu 5.4
(SG Ready A and SG Ready B).
Closed or open switch means one of the following:
Blocking (A: Closed, B: Open)
"SG Ready" is active. The compressor in GreenMaster-
HP and additional heat are blocked.
Normal mode (A: Open, B: Open)
"SG Ready" is not active. No effect on the system.
Low price mode (A: Open, B: Closed)
"SG Ready" is active. The system focuses on costs
savings and can for example exploit a low tariff from
the electricity supplier or over-capacity from any own
power source (effect on the system can be adjusted
in the menu 4.1.5).
Overcapacity mode (A: Closed, B: Closed)
"SG Ready" is active. The system is permitted to run
at full capacity at over capacity (very low price) with
the electricity supplier (effect on the system is set-
table in menu 4.1.5).
(A = SG Ready A and B = SG Ready B )
+Adjust
Using +Adjust, the installation communicates with the
underfloor heating's control centre* and adjusts the
heating curve and calculated supply temperature ac-
cording to the underfloor heating system's reconnec-
tion.
Activate the climate system you want +Adjust to affect
by highlighting the function and pressing the OK but-
ton.
28
Chapter 5 |
Electrical connections
*Support for +Adjust required
Caution
This accessory may require a software update
in your GreenMaster-HP. The version can be
checked in the "Service info" menu 3.1. Visit
http://www.myupway.com and click on the
"Software" tab to download the latest soft-
ware to your installation.
Caution
In systems with both underfloor heating and
radiators, ECS 40/41 should be used for op-
timum operation.
External blocking of functions
An external switch function can be connected to
GreenMaster-HP for blocking various functions. The
switch must be potential-free and a closed switch results
in blocking.
NOTE
Blocking entails a risk of freezing.
Functions that can be blocked:
hot water (hot water production). Any hot water circu-
lation (HWC) remains in operation.
heating (blocking of heating demand)
compressor
internally controlled additional heat
tariff blocking (additional heat, compressor, heating,
cooling and hot water are disconnected)
Possible selections for AUX output
Indications
alarm
cooling mode indication (only applies if there are
cooling accessories)
external heating medium pump
Controls
ground water pump
circulation pump for hot water circulation
additional heat in charge circuit
external heating medium pump
External circulation pump, ground water pump or hot
water circulation pump is connected to the common
alarm relay as illustrated below. If the pump has to work
in the event of alarm, the cable is moved from position
2 to position 3.
GreenMaster-HP