Fire alarm type 1
The exhaust air damper (QM40) closes
The fire bypass damper (QM41) opens
Exhaust air fan (GQ2) runs at fixed fire flow, which is
set in menu 5.3.22.
Fire alarm type 2
Exhaust air fan (GQ2) stops
The exhaust air damper (QM40) closes
fire alarm temperature BT20
Make settings here for the speed at which the fan will
run in the event of fire.
Setting range: 38–45%
Factory setting: 38%
fan speed during fire alarm
Make settings here for the speed at which the fan will
run in the event of fire.
Setting range: 0–100%
Factory setting: 70%
filt. alarm press.
Make settings for alarm for a clogged filter here. When
the set value is exceeded, an alarm is triggered.
Setting range: 100–300 Pa
Factory setting: 150 Pa
Menu 5.6 - forced control
You can make the settings for forced control of Green-
Master-HP here. Forced control must only be used by
users with a good knowledge of the system. When forced
control is activated, the alarm functions are disabled.