Installing the Virtual Services Platform 8000 Series
Airflow direction
The airflow direction for the VSP 8200 Series and the VSP 8400 Series is front-to-back.
Install a Fan Module
The VSP 8000 Series comes with four 12–V fan modules for switch cooling.
Figure 25: Fan module
There are four sensors inside the chassis that monitor the temperature. These sensors send
information to a controller that automatically regulates the fan speed to maintain the proper
temperature.
• If any sensor exceeds its threshold, an alarm is triggered and the log is generated in the
format:
Temperature Sensor [CPU | MAC | PHY1 | PHY2] is ([value] C) has exceeded the alarm
threshold temperature ([value] C)
Important:
The system does not shutdown when it exceeds the threshold temperature.
• When the temperature cools by 2° below the threshold, the alarm clears and the log is
generated in the format:
Temperature Sensor [CPU | MAC | PHY1 | PHY2] overheat temperature alarm cleared
The following table shows the types of sensors and the corresponding threshold values:
Table 18: Sensor threshold values
Sensor name
CPU
MAC
PHY1
PHY2
Use this procedure if a fan fails and you have to replace it.
March 2020
Warning threshold
45
50
50
50
Installing the VSP 8000 Series
Critical threshold
55
60
60
60
80