Camflex Rotary Valve Mounting
5. Loosely assemble the FVP to the mounting bracket using only the two top 1/4 - 20
UNC socket-head cap screws.
6. Pull the FVP away from the actuator to allow the pin on the valve side lever to be
inserted into the slot in the FVP lever under the anti-backlash spring (Figure 28).
7. Assemble the two bottom bolts and securely tighten all four bolts.
Figure 28 FVP110 Mounted on a Camflex Valve (Side View)
This device may be damaged if the feedback shaft exceeds
CAUTION
its allowable limit. When mounting the FVP110 on a rotary
valve, ensure that the rotation of the feedback shaft is
correct by checking that:
Range of rotation angle of shaft: within ±45° from
horizontal level
Minimum span: 20°
Maximum span: 90°
Mechanically allowable rotation angle: ±55°