Camflex Rotary Valve Mounting - GE FVP110 Maintenance Manual

Table of Contents

Advertisement

Camflex Rotary Valve Mounting

1. Turn the A/M selector switch clockwise to M (Figure 26).
2. Vary the pneumatic pressure output to the valve actuator by changing the regulator
output pressure by more than 70 kPa (approximately), regardless of the input signal
of the FVP110. For an FVP110 equipped with pressure gauges, you can read the
output pressure to the actuator.
When using the Double Acting Type, the pneumatic pressure can only be varied
from OUT1 to the valve actuator. The pressure is always 0% from OUT2 to the
valve actuator. The valve position is not always in accord with the regulator
pressure.
3. Turn the A/M selector switch counterclockwise until the stopper pin touches the side
of the FVP110's casing to ensure the switch position changes to A.
Camflex Rotary Valve Mounting
This section describes the procedure for mounting the FVP on rotary control valves,
using GE Masoneilan rotary valves as an example. Refer to Figure 27 on page 44 and
Figure 28 on page 45 for details.
Tools Required
5/32 and 3/16" Hex Wrench with tee handle
3 mm, 4 mm, and 5mm Hex Wrench
7/16" Combination Wrench
The mounting bracket for the Camflex
One square side has a large hole in the center with four smaller holes above, below, left
and right of the center hole; this side mounts to the actuator.
The other square side has a large hole that is a little bit off center and two rows of two
smaller holes above and below the large hole; this side mounts to the FVP.
Figure 26 A/M Selector Switch
*
has four sides, two square and two rectangular.
43
Installing the FVP110 on the

Hide quick links: