GE FVP110 Maintenance Manual page 230

Table of Contents

Advertisement

GE Energy
Relative
Index
Parameter
Index
29
17529 ARITH_TYPE 0
30
17530 BAL_TIME
31
17531 BIAS
32
17532 GAIN
33
17533 OUT_HI_LIM
34
17534 OUT_LO_LIM 0%
35
17535 UPDATE_EV
T
36
17536 BLOCK_ALM
Table 67 AR (Arithmetic) Block Parameters (Continued)
Default
Name
(factory
setting)
0
0
100%
FVP 110 Fieldbus Valve Positioner Manual
Write
The identification number of the arithmetic
algorithm. 1 to 9.
This specifies the time for the internal working
value of bias or ratio to return to the operator
set bias or ratio, in seconds.
The bias value used in computing the function
block output, expressed in engineering units.
OUT_SCALE +/- 10%.
Dimensionless value used by the block
algorithm in calculating the block output.
Limits the maximum output value.
OUT_SCALE +/- 10%.
Limits the minimum output value. OUT_SCALE
+/- 10%.
Read only
An alert for any change in the static data.
This alert can notify interface devices that
keep track of changes that one or more
changes have occurred. The relative
parameter index and its associated block
index is included in the alert, along with the
new value of ST_REV
Shows the contents of an alarm event upon
occurrence.
214
Description