AO Block

AO Block

Simulation Enable

This is a method for causing the AO block to activate the simulation status. When a
block is in the simulation status, you can apply simulated inputs to the block to let the
block function with that input, and check the actions of the function block application
and alarm processing. Since the simulation function is disabled to run normally in
consideration of the nature of its functionality, when using this method, the simulation
function needs to be rendered active by doing either of the following:
Write REMOTE LOOP TEST SWITCH" to SIM_ENABLE_MSG in the resource
block.
Turn on the SIM.ENABLE hardware switch on the YPV110's amplifier assembly
(see "Simulation Function" on page 113).
Simulation enabling procedure:
1. Check that the simulation switch is ON (active).
2. Check the AO block mode.
3. Change the value of SIMULATE.status to Enable.
4. Set the simulated input value in SIMULATE.value.

Simulation Disable

This is a method for disabling the simulation function of the AO block.
Simulation disabling procedure:
1. Confirm whether the simulation function can be disabled.
2. Change the value of SIMULATE.status to Disable.
3. The method displays a message announcing that block alarms will not be reset until
both the hardware switch and software switch in the resource block for enabling
execution of the simulation function are turned off.
237
DD Methods and DD Menu