GE FVP110 Maintenance Manual page 146

Table of Contents

Advertisement

GE Energy
Value
100
Cycle count limit exceed
101
Travel limit exceed
102
Total open limit exceed
103
Total close limit exceed
Total near close limit exceed
104
110
Temperature out of range
111
Pressure sensor out of range
112
Position sensor out of range
Deviation warning
113
Servo output drift warning
114
120
Temperature sensor failure
121
Pressure sensor failure
Severe servo output drift
122
Deviation error
123
124
Position sensor failure
125
A/D converter failure
Table 36 XD_ERROR
Comment
TOTAL_CYCLE_COUNT has reached CYCLE_COUNT_LIM.
TOTAL_TRAVEL has reached TRAVEL_LIM.
TOTAL_OPEN_TIME has reached OPEN_TIME_LIM.
TOTAL_CLOSE_TIME has reached CLOSE_TIME_LIM.
TOTAL_NEAR_CLOSE_TIM has reached
NEAR_CLOSE_TIME_LIM.
The measured temperature is out of range.
The measured pressure is out of range.
The measured valve position is out of range.
The deviation between the setpoint and measured valve
position has exceeded DEVIATION_LIM continuously for the
period specified by DEVIATION_TIME_TH [1].
SERVO_OUTPUT_SIGNAL has reached
SERVO_WARN_LO_LIM or SERVO_WARN_HI_LIM and has
continued in excess of SERVO_TIME_TH. This is not
applicable for tight-shut or full-open actions, or when the period
specified by SERVO_TIME_TH is less than 0.
Temperature sensor failed
Pressure sensor failed,
SERVO_OUTPUT_SIGNAL has reached 10% or 90%, and has
continued in excess of SERVO_TIME_TH. This is not
applicable for tight-shut or fullopen actions, or when the period
specified by SERVO_TIME_TH is less than 0.
The deviation between the setpoint and measured valve
position has exceeded DEVIATION_LIM continuously for the
period specified by DEVIATION_TIME_TH [2].
Position sensor failed
A/D converter failed
FVP 110 Fieldbus Valve Positioner Manual