GE FVP110 Maintenance Manual page 222

Table of Contents

Advertisement

GE Energy
Relative
Index
Parameter
Index
7
8007
PV
8
8008
SP
9
8009
OUT
10
8010
PV_SCALE
11
8011
OUT_SCALE
12
8012
GRANT_DEN
Y
13
8013
CONTROL_O
PTS
14
8014
STATUS_OP
TS
15
8015
IN
16
8016
PV_FTIME
17
8017
BYPASS
18
8018
CAS_IN
19
8019
SP_RATE_D
N
20
8020
SP_RATE_U
P
21
8021
SP_HI_LIM
22
8022
SP_LO_LIM
23
8023
GAIN
Table 65 PID Block Parameters (Continued)
Default
Name
(factory
setting)
0-100%
0-100%
0
0x0000
0x0000
0
0
1
0
+INF
+INF
100
0
1
FVP 110 Fieldbus Valve Positioner Manual
Write
Indicates the primary analog value (or the
corresponding process value) used to execute
the specified actions, and the status of that
value.
Auto
Setpoint of the block.
Man
Value and status of output.
O/S
Upper and lower scale limit values used for
scaling of the input (IN) value.
O/S
Upper and lower scale limit values used for
scaling of the control output (OUT) value to the
values in the engineering unit.
Option to control access from the host
computer and local control panel to tuning and
alarm parameters.
O/S
Defines block actions depending on block
status conditions.
O/S
Defines options for control actions of block.
Controlled-value input.
Time constant (in seconds) of the first-order lag
filter applied to IN
Man
Determines whether to bypass control
computation.
1 = off; do not bypass.
2 = on; bypass.
Cascade setpoint.
Rate-of-decrease limit for setpoint (SP)
Rate-of-increase limit for setpoint (SP)
Upper limit for setpoint (SP)
Lower limit for setpoint (SP)
Proportional gain (= 100 / proportional
band).
206
Description