GE Energy
❑
To maintain the degree of ingress protection IP65 according to EN 60529 special
care must be taken to avoid water entering the breathing and draining device when
the valve positioner is mounted with the feedback shaft in the upright position.
Note 4. Operation
❑
Keep strictly the WARNING on the label on the positioner.
WHEN THE AMBIENT TEMP. ≥ 70° C,
USE HEAT-RESISTING CABLES .≥ 90° C.
❑
Take care not to generate mechanical sparking when accessing to the instrument
and peripheral devices in a hazardous location.
Note 5. Maintenance and Repair
❑
The instrument modification or parts replacement by other than authorized
representative of GE Masoneilan is prohibited and will void KEMA Flameproof
Certification.
C) CENELEC ATEX Type of Protection n
Note 1. Model FVP110 Advanced Valve Positioner with optional code /KN25.
❑
Applicable standard: EN60079-15:2003
❑
Referential standard: IEC60079-0:1998, IEC60079-11:1999
❑
Type of Protection and Marking Code: EEx nL IIC T4
❑
Group: II
❑
Category: 3G
❑
Ambient Temperature: –40 to 60 °C
❑
Enclosure: IP65
Note 2. Electrical Data
Ui = 32 Vdc
Ci = 1.76 nF
Li = 0 μH
When using a power supply not having a nonincendive circuit,
WARNING
please pay attention not to ignite in the surrounding
flammable atmosphere.
In such a case, we recommend using wiring metal conduit in
order to prevent the ignition.
FVP 110 Fieldbus Valve Positioner Manual
26