TECHNICAL SPECIFICATIONS
MODEL
NATURAL GAS MAX. THERMAL POWER
NATURAL GAS MIN. THERMAL POWER
¹) NATURAL GAS EMISSIONS
NATURAL GAS OPERATION
NATURAL GAS MAX. HEATING CAPACITY
NATURAL GAS MIN. HEATING CAPACITY
NATURAL GAS MIN. PRESSURE
NATURAL GAS MAX PRESSURE
PROPANE GAS MAX. THERMAL POWER
PROPANE GAS MIN. THERMAL POWER
PROPANE GAS MAX. HEAT CAPACITY
PROPANE GAS MIN. HEAT CAPACITY
PROPANE GAS MIN PRESSURE
PROPANE GAS MAX PRESSURE
²) PROPANE EMISSIONS
DIESEL OIL MAX. HEATING CAPACITY
DIESEL OIL MIN. HEATING CAPACITY
DIESEL OIL MAX THERMAL POWER
DIESEL OIL MIN. THERMAL POWER
³) DIESEL EMISSIONS
DIESEL VISCOSITY
DIESEL OPERATION
50 Hz FAN MOTOR
50Hz FAN MOTOR RPM
60Hz FAN MOTOR
50 Hz IGNITION TRANSFORMER
60 Hz IGNITION TRANSFORMER
VOLTAGE 50Hz
VOLTAGE 60Hz
50Hz* ELECTRICAL POWER
60Hz* ELECTRICAL POWER
DEGREE OF PROTECTION
EQUIPMENT
FLAME DETECTOR
SOUND PRESSURE**
WEIGHT WITH PACKING
WEIGHT WITHOUT PACKING
Calorific power lower than reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9.45 kWh/Stm³ = 34.02 MJ/Stm³
Propane gas: Hi = 24.44 kWh/Stm³ = 88.00 MJ/Stm³
For different types of gas and pressure values, please contact our sales department.
Lower calorific power:
Diesel oil: Hi = 11.86 kWh/kg = 42.70 Mj/kg
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
* Total absorption at start with ignition transformer on.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations.
CO emissions, natural gas/propane ≤ 100 mg/kWh
mg/kWh
hPa (mbar)
hPa (mbar)
hPa (mbar)
hPa (mbar)
mg/kWh
mg/kWh
6 / 44
0006160077_201802
TBML 350 ME
kW
3600
kW
600
Class 3
electronic modulation
Stm³/h
381
Stm³/h
63
53
500
kW
3600
kW
600
Stm³/h
147
Stm³/h
24.5
25
500
Class 3
kg/h
303
kg/h
63
kW
3600
kW
750
Class 2
1.5° E - 20° C
electronic modulation
kW
7
r.p.m.
2930
kW
9
10 kV - 30 mA
10 kV - 30 mA
3N ~ 400 V ± 10%
3N ~ 380 V ± 10%
kW
9.9
kW
11.6
IP 54
BT 340
UV photocell
dBA
85.8
kg
390
kg
350