INSTALLATION AND OPERATING MANUAL ATyS FT Fast transfer UL 1008 Transfer switching equipement www.socomec.com To download, brochures, catalogues and technical manuals.
WARNING ! This product can expose you to chemicals including bisphenol A, which is known to the State of California to cause birth defects. For more information go to : www.P65Warnings.ca.gov ATyS FT - 549867A - SOCOMEC...
2. INTRODUCTION ATYS FT (Fast Transfer) are open type, two position automatic transfer switches listed to UL 1008 for standby, legally required andemergencysystems.Theyaredesignedspecificallyforuseinlowvoltagepowerapplicationsforthesafetransferofa load supply between a normal and an alternate source. These automatic transfer switches are designed to meet NFPA 110 requirements for NFPA 110 for Emergency and Standby Power systems and the National Electrical Code (NEC) Articles 700, 701 and 702.
For further details refer to the product instruction manual under chapter “Spares and Accessories”. Spares • ATyS C66 Controller (ref. 16000066). • UL 1008 ATyS FT (ref. 960XXXXX). • Connector kit (ref. 16090002). Source 2 • Controller Nema 3R gasket (ref. 16090001).
Page 8
Ilsco D3096 2 terminal lugs. Power cable connections : For 100A use 1/0 AWG / For 200A use 250 KCMIL / For 260A use 300 Kcmil / For 400A use 600 Kcmil copper cables. ATyS FT - 549867A - SOCOMEC...
Page 9
0.5 N.m / 4.4 Lb.in switch shown above to maintain any unused cables used to maintain cables connected to (for 2P, 2P+N or 3P switches). the auxiliary contacts. ATyS FT - 549867A - SOCOMEC...
Page 10
NC : Ground Connection point for I/O 10 optional accessories & Digiware* DIGIBUS RJ 45 digiware cable digiware connection (must use 24 VDC input) * For more information check I/O module instruction sheet ref 545597 ATyS FT - 549867A - SOCOMEC...
Page 11
In STEP 5/8 of the wizard config make sure the network detected matches your network. In STEP 6/8 make sure the “switch technology” parameter is set to “ATyS FT”. If a fault is shown on the controller, correct the associated fault and clear by doing a long press (>3s) on the lamp test button.
Page 12
Ensure that all is closed properly before putting back in service. Open the cover and click in place and In case any part of the ATyS FT switch is found to be damaged in any way, replace the open the arc chute complete switch.
Page 13
Make sure contact is correctly activated PERIODIC MAINTENANCE The ATyS FT shall be maintained in accordance with industry standards and as per instructions in the ATyS FT Place the transparent instruction sheet. plastic piece to cover As per NFPA 110 requirements for emergency and standby power systems the ATyS FT should be inspected the auxiliary conacts and should be exercised under load at least monthly.
- 1 Cable harness for connections between the switch and the controller - 20Cabletiesforharnessfixationpoints All other components described in this instruction sheet are accessories and are sold separately. If any components are missing from the list described above contact your local Socomec contacts. ATyS FT - 549867A - SOCOMEC...
4.1. ATyS FT (fast transfer) switching mechanism The ATyS FT is a I-II position UL 1008 transfer switch, available from 100 to 400A. Here is a view of the customer accessible elements on the switching mechanism: 1. Plastic cover for off load manual operation 2.
The ATyS C66 controller is an ATS controller designed to function as an emergency system automatic transfer switch when used with the ATyS FT and ATyS DT switching mechanism. In this instruction manual we will go over the basic settings for the association of the ATyS C66 with the ATyS FT switch, for moreinformationonthedetailedconfigurationoftheC66downloadthefollowinginstructionsheet: https://www.socomec.us/wp-content/uploads/2020/04/ATYS-C66-INSTRUCTION-MANUAL_INSTRUCTION-...
4.3. ATyS FT Cable Harness The ATyS FT is delivered with a wiring harness, which includes all connections points for sensing, supply voltage to the coils and controller, and input/outputs from the switch mechanism to the controller. Cable harnesses are in compliance with pollution degree III.
4.3.2. With Transformer connection points Ref: 9697 4000 for use with ATyS FT ref 98AX XXXX (X variable number depending on number of poles and rating of the switch). ATYS FT CONTROLLER 70 76 75 74 73 72 71 22 24 21...
4.4. Optional accessories The accessories listed below are not included in the ATyS FT kit and must be ordered separately. Terminal screens Top and bottom terminal screens to protect from direct contact to the terminals. These protection screens can be locked and secured on the switch, are pre-cut for all compatible wire sizes and include holes for voltage and heat sensing.
For the connection between the controller and the accessories and between modules, a RJ45 Digiware cable is needed. There are different sizes available: Length (m) Quantity Reference 4829 0181 4829 0188 4829 0182 4829 0183 4829 0184 4829 0186 4829 0187 50 m reel + 100 connectors 4829 0185 ATyS FT - 549867A - SOCOMEC...
0: spare switch for networks up to 480 VAC 0: Without solid neutral 8: ATSE assembly for 480 V.a.c 3 wire network 1: With solid neutral A: ATSE Assembly for networks up to 480 VAC ATyS FT - 549867A - SOCOMEC...
• Switch mechanism: From: -32° to 131°F (0 to +55°C) Max 380 A at 55°C for 400A switches For a more precise calculation of the temperature derating for your application please contact Socomec. • Wire harness (-20°C to +70°C) 4.6.1.2. Hygrometry •...
4.6.3. ATyS FT Volume and shipping weight by reference: Weight (kg) N° of Solid Reference Rating Network type Volume Gross Poles Neutral Number Without Up to 240 VAC 96A0 2010 23.37 10.6 57.72 26.18 With Up to 480 VAC 96A1 2010 25.35...
Source 1 Mounting orientation Socomec recommends connecting the Emergency (or alternate) source on the Source 2 power connections and the Normal (primary) source on the Source 1 power connectors. However, it is possible to invert the position of the Normal and emergency sources on both the controller and on the switch;...
Page 27
Insert the oblong holes of the mounting legs in the top side screws. STEP 3: Positioning the switch Position the two-bottom mounting legs on the bottom screws. Theswitchisnowstableandrestingonthefourscrews,andthentightenthefourscrewsuntiltheswitchisfixedsecurely into place. (For tightening torque and screw type, refer to the enclosure backplate manufacturer information). ATyS FT - 549867A - SOCOMEC...
(2 screws per side). Tighten at 1.77 lb.in (0.2 N.m). Insert the 4 door mounting screws in the designatedslot and push back to lock in place. Example of cable way. 10 mm 10 mm Screw Tightening torque PH1 / 0.2 Nm / 1.77 lb.in ATyS FT - 549867A - SOCOMEC...
STEP 2: Fixing the controller on the backplate Fix the controller through the mounting legs to the backplate, maximum screw diameter 0.22in/6mm. Screwsnot deliveredwithproduct Note: screws for backplate mounting are not delivered with the product ATyS FT - 549867A - SOCOMEC...
6.4. Mounting the ATyS FT cable harness 6.4.1. Fixing the faston connectors As shown on the wire harness schematics in chapter 4.3 the wiring harness includes 5 fast on connectors per source (5 connectors for source 1 and 5 connectors for source 2).
Page 31
T2B' 480 VAC + transfo S1A &** T1A S1B &**T1B T1A' T1B' *Position and connection points shown in schematic above ** “&” indicates that both faston connectors must be placed on the designated pole. ATyS FT - 549867A - SOCOMEC...
(for 2P, 2P+N or 3P switches). 6.4.3. Controller side connectors 6.4.3.1. Connectors with harness The remaining connectors of the cable harness must be placed on the controller; the location of these connectors is highlighted below: ATyS FT - 549867A - SOCOMEC...
As indicated in «Fixing the faston connectors», page 30 of this chapter wires with faston connectors must be maintained in place using cable ties. AfterfixingtheFASTON maintainthe wiresinplace wiring connexion point. The wires should be passed along the cable duct as shown below (this includes cables with unused Faston connectors). SOURCE 2 ATyS FT - 549867A - SOCOMEC...
Page 35
(cf. image below): Thisswitchincludesadditionalcabletiefixationpointsasshowinthefollowingimage. For example, these can be used to maintain cables in place when connecting wires to the customer position auxiliary contacts. ATyS FT - 549867A - SOCOMEC...
Cable ties used should be adapted according to the position of the door: Left side hinge door Right side hinge door cables must be more than 0.4 in (10mm) away from the RTC battery cover and USB connector. ATyS FT - 549867A - SOCOMEC...
*Socomec recommends having fixation points every 7.9 inches (200 mm) in order to insure the harness is correctly maintained. +/- 7.9 in +/- 200 mm Not supplied ATyS FT - 549867A - SOCOMEC...
For 250, 300 & 600 KCMIL (200 , 260 400A) break off all removable parts (highlighted on the picture). For 1/0 & (100A ) do not remove any parts. Fix the terminal shrouds in place and push back. Whenfixingtheshroudsmakesurethepiecesfitintheswitchasshownintheimageabovethenpushbacktoclipinplace. ATyS FT - 549867A - SOCOMEC...
6.5.3. Extra auxiliary contact and cover The ATyS FT switches are delivered with two Pre-installed C-Form auxiliary contacts (one for each position) on the left side of the switch: The auxiliary contacts have the following characteristics: Terminal tightening torque 7.9 lb.in / 0.9 Nm...
Page 41
Finally place the plastic cover, push the cover to clip into the two inter-contact barriers. This barrier can then be locked in place using cable ties. (To remove squeeze the top and bottom parts of the transparent piece and pull out). ATyS FT - 549867A - SOCOMEC...
An end-of-the-bus resistor is necessary for a correct communication between the modules and the controller: Quantity Part number 4829 0180 MADE IN FRANCE CURRENT TRANSFORMERS : 1A or 5A TRANSFORMATEURS DE COURANT : 1A ou 5A SOURCE S2 SOURCE S1 GND GND 120Ω RS485 ATyS FT - 549867A - SOCOMEC...
Page 43
The connection between modules and to the ATyS C66 Digiware input is on the side of the controller by means of an RJ45 connector and after this the other modules are daisy chained (up to 6 modules). ATyS FT - 549867A - SOCOMEC...
7. CONFIGURATION This document will cover basic programming of the C66 controller in the ATyS FT application, for more details on timers, specificfunction,input/outputconfigurationsandothersrefertotheATySC66instructionsheet(549868)availableonthe Socomec website: https://www.socomec.us/range/atys-c66/ WhenpoweredupforthefirsttimetheC66willpromptuserstogothroughtheinstallationwizard. Thefirstoutof8questionswillbethelanguage.Usercanchoosebetweenthefollowing3languages: • English • French • Spanish Then it will follow the option to start the wizard with the following options: •...
Page 45
Important: Switch technology must be set to “ATyS FT”. The 7th step is not affecting the functioning of the transfer switch but permits the user to select a name for the product. As default, it’s ATyS C66, but it can be changed for any combination of letters, numbers and signs, for instance, “Cooling”, “Line...
Page 46
FAIL TO SYNC OPT for a correct transfer window, “FORCE TRANSFER” will initiate a transfer USER CHOICE at the end of the configured IN PHASE RESEARCH DELAY without checking the synchronization of the sources. ATyS FT - 549867A - SOCOMEC...
- Using Standard operation handle (marked “FAST OPERATION” on the image below) which will operate contacts at the same speed as they would normally operate using electrical operation, independently of the speed used to operate the handle. ATyS FT - 549867A - SOCOMEC...
Note: in manual mode, if a source is lost, the genset (if any) will start and the controller will not force an automatic transfer. The controller will remain in manual mode until reverted to Auto by the user. ATyS FT - 549867A - SOCOMEC...
There are no user serviceable parts in the controller except for the RTC replaceable battery. In case of a malfunction, do not attempttoopentheproductandcontactyourlocalsupplier.Inthiscasethemodel,firmwareversionandserialnumberofthe unit will be useful to provide and can be found inside the ABOUT menu as well as on the product labels and QR code on the rear side of the controller. ATyS FT - 549867A - SOCOMEC...
Page 51
5. P lacethenewbatteryonthecorrectside(polarity)intheholderfromthepcbandpushwiththefingeruntilitreaches the position of the old one. 6. Putbacktheplasticcoveronthesideofthecontrollerandpressureslightlyuntilitperfectlyfits. 7. Connect back the terminals to the controller 8. Power up and adjust time and date For battery replacement, use a BR2032 coin-type battery cell. ATyS FT - 549867A - SOCOMEC...
- Increase the genset startup timer to allow more time. time to start the genset. Input 3 linked to the switch manual handle Check that the cover protecting the manual handle COVER OPEN cover is active. is correctly screwed in place. ATyS FT - 549867A - SOCOMEC...
ANNEX I. SINGLE LINE DIAGRAMS The following single line diagrams show he wiring each include a power section (wiring of the poles to each of the sources and load) and control circuit (includes voltage sensing and order connection from the controller to the switch).