548695E
ATyS FT
100 A, 200 A, 260 A, 400 A

Preliminary operations

Check the following upon delivery and after removal
of the packaging:
• Packaging and contents are in good condition.
• The product reference corresponds to the order.
• Contents should include:
Qty 1 x ATyS FT
Qty 1 x C66 Controller
Qty 1 x Harness
Warning
Risk of electrocution, burns or injury to persons
and / or damage to equipment.
This Quick Start is intended for personnel trained in
the installation and commissioning of this product.
For further details refer to the product instruction
manual available on the SOCOMEC website.
• This product must always be installed and
commissioned by qualified and approved personnel.
• Maintenance and servicing operations should be
performed by trained and authorized personnel.
• Do not handle any control or power cables connected
to the product when voltage may be, or may become
present on the product, directly through the mains or
indirectly through external circuits.
• Always use an appropriate voltage detection device
to confirm the absence of voltage.
• Ensure that no metal objects are allowed to fall in
the cabinet (risk of electrical arcing).
Failure to observe good engineering practices as well
as to follow these safety instructions may expose the
user and others to serious injury or death.
Risk of damaging the device.
In case the product is dropped or damaged in any
way it is recommended to replace the complete
product. Installation standards must be respected.

Accessories

Accessories are not included and must be
ordered seperatly
• Terminal shrouds (see step 6A).
• Additional aux contacts (ref. 96990021).
• Digiware I/O 10 (ref. 48290140).
• Transformer 480 - 240 VAC (SPARTAN SP350MQMJ).
• Controller 24 VDC aux power supply
(6W minimum type SELV) mandatory with I/0 10 Modules.
• Power terminal lugs (see step 1D).
For further details refer to the product instruction
manual under chapter "Spares and Accessories".

Spares

• ATyS C66 Controller (ref. 16000066).
• UL 1008 ATyS FT (ref. 960XXXXX).
• Connector kit (ref. 16090002).
• Controller Nema 3R gasket (ref. 16090001).
• Controller mounting screws (ref. 16090004).
• Controller mounting feet (ref. 16090005).
• Cable harness without transfomer (ref. 96964000).
• Cable harness with transfomer (ref. 96974000).
CORPORATE HQ CONTACT:
SOCOMEC SAS,
1-4 RUE DE WESTHOUSE,
67235 BENFELD, FRANCE
www.socomec.com
To download, brochures,
catalogues and technical manuals:
www.socomec.us/resources/
Installation and Commissioning
STEP 1
STEP 2
Cabinet / Back
Connecting
Plate Installation
the cable harness
Reference configurator
0: spare switch for networks up to 480 VAC
8: ATSE assembly for 480 V.a.c 3 wire network
A: ATSE Assembly for networks up to 480 VAC
1A

Switch installation

For Use on a Flat Surface of a Types
1, 3R, 12 and/or 12k enclosure.
STEP 3
STEP 4
Controller
interface
N° of poles
2: 2P
3: 3P
4: 4P
9 6 X X X XXX
0: Without solid neutral
1: With solid neutral
Load
Mounting orientation
Non contractual document. Subject to change without notice.
QUICK START GUIDE
STEP 5
STEP 6
Manual operation
Accessories
Rating
010: 100 A
020: 200 A
026: 260 A
040: 400 A
Source 2
PE
Source 1
EN

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ATyS FT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for socomec ATyS FT

  • Page 1 For further details refer to the product instruction manual under chapter “Spares and Accessories”. Spares • ATyS C66 Controller (ref. 16000066). • UL 1008 ATyS FT (ref. 960XXXXX). • Connector kit (ref. 16090002). Source 2 • Controller Nema 3R gasket (ref. 16090001).
  • Page 2 Product dimensions Switch & minimum enclosure size dimensions (4th pole represented with lugs installed.) Dual Dimensions in/mm 144,8 4x Ø 0.41 4x Ø 10.5 4.23 7.13 min. 2.75 107,5 min. 70 Switch top view Controller dimensions 2.52 9.45 63,90 1.89 8.66 48,10 SWITCH DIMENSIONS...
  • Page 3 Mounting & connecting controller Door mounting Insert the 4 door For use on a flat suface of Types 1, 3R, 12 and/or 12K enclosure. mounting screws in the designated slot and push back to clip in lock in place. Screw Tightening torque PH1 / 0.2 Nm 1.77 lb.in Gasket for Type 3R/12 Backplate mounting...
  • Page 4 Mounting & connecting the cable harness For details on the cable harness wiring diagram and integration see Cable harness Quickstart guide ref 551401. Cable harness without transformer (ref. 96964000) delivered with 96AX XXXX products. Cable harness for connections with transformer (ref. 96974000) delivered with 968X XXXX products. Note: transformers not delivered with the product.
  • Page 5 Connection of harness on the switch Connect the faston on the switch connexion according to your network and the table below: VOLTAGE TRANSFORMER RTSE FASTON CONNECTIONS 480 VAC 240 VAC PRIMARY SECONDARY NETWORK TYPE TYPE SOURCE S2A & 201 None None 240 VAC S1A &...
  • Page 6 In STEP 5/8 of the wizard config make sure the network detected matches your network. In STEP 6/8 make sure the “switch technology” parameter is set to “ATyS FT”. If a fault is shown on the controller, correct the associated fault and clear by doing a long press (>3s) on the lamp test button.
  • Page 7 Ensure that all is closed properly before putting back in service. Open the cover and click in place and In case any part of the ATyS FT switch is found to be damaged in any way, replace the open the arc chute...
  • Page 8 Make sure contact is correctly activated PERIODIC MAINTENANCE The ATyS FT shall be maintained in accordance with industry standards and as per instructions in the ATyS FT Place the transparent instruction sheet. plastic piece to cover As per NFPA 110 requirements for emergency and standby power systems the ATyS FT should be inspected the auxiliary conacts and should be exercised under load at least monthly.