One must also refer to and respect markings on the product prior to installation and commissioning for values and limits specific to that product. • Using the product outside the intended scope, outside SOCOMEC recommendations or outside the specified ratings and limits can cause personal injury and/or damage to equipment.
IEC 60947-3 standards. As a Class PC ATSE, the ATyS g M is capable of “making and withstanding short circuit currents” assigned to IEC 60947- 3 utilization categories of up to AC23A, GB 14048-11, IEC 60947-6-1 and equivalent standards with utilization categories of up to AC33B.
* 3 inputs / 3 outputs (programmable). ** Product reference is different: communication by RS485 connection (MODBUS) allows up to 31 ATyS M to be connected to a PC or a PLC over 1500 m. ATyS g M - 542933D - SOCOMEC...
2A 30 Vdc 1309 10 CORPORATE HQ CONTACT: 0.5A 230Vac Generating set starting SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE Pmax : 60W or 125VA Umax : 30Vdc or 230Vac Non contractual document. 542955E Subject to change without notice.
Page 9
2 modules 250V AC 5A AC1 21/22/24 Changeover switch in position II 30 Vdc 5 A Pozidriv PZ2 - 1 Nm 01/02/04 250V AC 5A AC1 Changeover switch in position 0 30 Vdc 5 A ATyS g M - 542933D - SOCOMEC...
Page 10
• Check the changeover switch position Configurable to I-0-II (see step 1). on the indicator before operating. 90º 90º Extension To simplify operation use the handle with the extension provided. 1x 4-8 mm (Max 8 Nm) ATyS g M - 542933D - SOCOMEC...
Page 12
2A 30 Vdc 1309 1011 Generating set starting CORPORATE HQ CONTACT: 0.5A 230Vac SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE Pmax : 60W or 125VA Umax : 30Vdc or 230Vac Non contractual document. 542932E Subject to change without notice.
2 modules 250V AC 5A AC1 21/22/24 Changeover switch in position II 30 Vdc 5 A Pozidriv PZ2 - 1 Nm 01/02/04 250V AC 5A AC1 Changeover switch in position 0 30 Vdc 5 A ATyS g M - 542933D - SOCOMEC...
Page 14
Configurable to I-0-II (see step 1). on the indicator before operating. 0,5 t 90º 90º 0,5 t Extension Slotte To simplify operation use the handle with the extension provided. 1x 4-8 mm (Max 8 Nm) ATyS g M - 542933D - SOCOMEC...
The power supply of ATyS g M is required to be 220 VAC -20% to 240VAC +20% at a frequency of 50/60 Hz and has been developed so as to meet most network configurations. Product’s working ranges: 230 / 400 VAC Version 127 / 230 VAC Version 230 VAC Version Umin Umax Umin Umax Umin Umax Ph-N Ph-Ph ATyS g M - 542933D - SOCOMEC...
For complete terminals, enabling connection of up to two 35mm² conversion, order 3 cables or one 70mm² cable. Each power connection times the reference. terminal is provided with separation screens. ATyS g M - 542933D - SOCOMEC...
** AC 33iB 160A according to GB 14048.11. This is a class A product. In a domestic environment, this product may cause radio interference in which case the user may be required to take adequate measures. ATyS g M - 542933D - SOCOMEC...
• Maximum storage temperature: +55 °C • 80 % humidity without condensation at 55 °C IP rating • IP41 in the SOCOMEC polycarbonate modular enclosure see page page 25 ø 1 mm • IP2x for non-enclosed modular product Protection class: Class 1...
Posidriv PZ2 8.2. Recommanded orientation Recommended 8.3. Dimensions of the single phase 8.4. Back plate mounted single phase MAX : 2 MAX : 2 73,5 73,5 4 mounting brackets 6x M6 screw - 2,5 Nm ATyS g M - 542933D - SOCOMEC...
MAX : 2 73,5 73,5 6 mounting brackets 6x M6 screw - 2,5 Nm 8.7. DIN rail mounted Tighten to avoid movement on the DIN rail. DIN RAIL IEC 60715 2 clips de verrouillage Posidriv PZ1 1 Nm ATyS g M - 542933D - SOCOMEC...
Allen size 4 44.1 lb-in 5,0 Nm Make sure that the bridging bar is fitted to the correct set of terminals. There are two references available: one for ratings up to 125A, and another for 160A rating. ATyS g M - 542933D - SOCOMEC...
There are two references available: one for ratings up to 125A, and another for 160A rating. 9.5. Terminal shrouds Ref. 2294 4016 °C °C °K °K 9.6. Sealable cover Single phase: ref. 1359 2000 ; three phase : ref. 1359 0000 ATyS g M - 542933D - SOCOMEC...
The enclosure must be wall-mounted using screws (not supplied). Recommended size: M6 50 mm (minimum). Weight : between 8 and 10 kg, depending on the accessories. Only 1 aux contact block may be installed when using this enclosure. 230mm (M6) 305 mm 150 mm Load Mains Genset ATyS g M - 542933D - SOCOMEC...
193 mm 10.2.1. Wiring in a polycarbonate enclosure Example: Neutral on the right Max cable size 25 mm² 10.2.2. Extension unit Ref. 1309 9007 Enables you to allocate additional space to the polycarobonate enclosure (ref. 1309 9006). ATyS g M - 542933D - SOCOMEC...
Rating conversion table for use in single phase and two-by-two parallel pole set up. (Max ambient temperature = 40 °C). Nominal current rating in three-phase (A) Nominal current rating in single-phase (2 poles in //) (A) ATyS g M - 542933D - SOCOMEC...
73 74 TEST resistive max 60W or 250VA / PRIORITY In case of three-phase without neutral configurations you must first configure the neutral position by wiring the product for the first time with a network 4NBL. ATyS g M - 542933D - SOCOMEC...
Open the AUTO/MANU cover. Step 2 Set DIP Switch 1 from 3P to 1P. Step 3 Set DIP Switch 1 from 1P to 3P. Step 4 Close the cover. End of the procedure for detecting the neutral position. ATyS g M - 542933D - SOCOMEC...
The product is delivered in the 0 position and in auto mode. Maximum control cables length = 10 m. In case of longer distance, use control relays. Source must always be connected as show above. Ensure that the product is in Manual Mode (front cover open). ATyS g M - 542933D - SOCOMEC...
250V AC 5A AC1 contact 21/22/24 Changeover switch in position II 24VDC 2A block AC13 - 250VAC - 2A 1309 1011 250V AC 5A AC1 01/02/04 Changeover switch in position 0 24VDC 2A AC13 - 250VAC - 2A ATyS g M - 542933D - SOCOMEC...
Position 0 Position II Position II C.A. Position I C.A. Position I 11-14 Closed 11-12 Open C.A. Position 0 01-04 Closed C.A. Position 0 01-02 Open C.A. Position II 21-24 Closed C.A. Position II 21-22 Open ATyS g M - 542933D - SOCOMEC...
4. Switch position indicators • Display of position I, 0, II. 5. Manual switching • Insert the Allen key (5.0 mm) provided and turn to switch manually. • Manual operation is not possible when padlocked. ATyS g M - 542933D - SOCOMEC...
• From position 0, turn anti-clockwise to get to position II • From position II, turn clockwise to get to position 0 • From position 0, turn clockwise to get to position I (Max 8 Nm) Do not force the product (Max 8 Nm). ATyS g M - 542933D - SOCOMEC...
Locking is only possible in manual mode (cover open). Pull on the locking handle to enable the interlock. Lock by 4 mm min inserting a padlock into the orifice provided for this purpose. 3/16” min 8 mm min 5/16” min ATyS g M - 542933D - SOCOMEC...
- a timer is counting down or out of range Fault and state of the product LED's LED ON LED OFF LED blinking Product OK or Fault Please wait S1-S2 not available Auto mode Manual mode Manual retransfer Fault reset ATyS g M - 542933D - SOCOMEC...
Product OK or Fault Please wait S1-S2 not available Auto mode Manual mode Manual retransfer CDT and DTT timers are fixed: Genset cooling time : 4min and validation of secondary network / backup source stability = 5 sec. ATyS g M - 542933D - SOCOMEC...
• Run a source I or source loss sequence II , • start a restoration sequence source I or source II . AUTOMATIC MODE Loss of source I / Source I return: Test on load source II source II ATyS g M - 542933D - SOCOMEC...
Produit en Source Source Écoulement d’une Groupe Groupe NORMAL PRIORITY II TEST from I to II de I vers II position I position I available présente absente missing temporisation counting available présent absent missing down ATyS g M - 542933D - SOCOMEC...
Page 41
Transfert I -> II Return of source 1 Loss of Loss of End of source 1 genset Transfert Genset CDT? I I -> I stop CDT = cool down timer fixed at 4 min. ATyS g M - 542933D - SOCOMEC...
Product in Source Source Timer is Genset Genset NORMAL PRIORITY II TEST from I to II position I available missing down available missing from I to II position I available missing counting available missing down ATyS g M - 542933D - SOCOMEC...
Page 43
Loss of source 1 Loss of genset Opening of contact 207/208 End of 5 s timer ? Genset End of Transfert stop CDT? I I -> I CDT = cool down timer fixed at 4 min. ATyS g M - 542933D - SOCOMEC...
End of 5s timer End of 5s timer +source 1 still +source 1 still available ? available ? Genset Transfert End of stop I I -> I CDT? CDT = cool down timer fixed at 4 min. ATyS g M - 542933D - SOCOMEC...
Timer is counting NORMAL PRIORITY II TEST Transfer from Product in Source Source missing Timer is NORMAL PRIORITY II TEST from I to II position I available missing down I to II position I available counting down ATyS g M - 542933D - SOCOMEC...
Page 46
Return of source 1 End of FT ? Transfert I -> II Return of source 1 Loss of source End of Loss of source End of 5 s timer ? Transfert I I -> I ATyS g M - 542933D - SOCOMEC...
Page 47
I -> II Opening of contact 207/209 Loss of source End of Loss of source 5 s timer ? End of Return of source 1 Transfert I I -> I Transfert End of I I -> I ATyS g M - 542933D - SOCOMEC...
• Contact 207/208 closed • Contact 207/209 open Loss of source Return source End of Transfert I -> II Return of source 1 Loss of source Return of End of source 2 Transfert I I -> I ATyS g M - 542933D - SOCOMEC...
Page 49
Loss of source End of 5 s timer ? Transfert I -> II Return of source 1 Impulsion of contact 207/209 End of Loss of source 5 s timer ? Transfert I I -> I ATyS g M - 542933D - SOCOMEC...
Good engineering practice is imperative whilst all necessary precautions must be taken to ensure that the intervention (whether directly or indirectly) remains safe in all aspects. The use of any Megohmmeter is prohibited on this product as the connection terminals are intrinsically connected to the sensing circuit. ATyS g M - 542933D - SOCOMEC...
• Step 1: Open the cover • Step 2 : Set DIP Switch 1 from 3P to 1P • Step 3 : Set DIP Switch 1 from 1P to 3P • Step 4 : Close the cover ATyS g M - 542933D - SOCOMEC...
Page 52
Check that automatic operation has not been inhibited by external control commands (terminals 207-210) Check if the ON Load test has started: The ON LOAD TEST starts. • On Load Test activated = Contact 207-209 Closed • On Load Test inhibited = Contact 207-209 Open ATyS g M - 542933D - SOCOMEC...
Page 53
Product available = A product which is within voltage and frequency limits without any internal failure. Open and close the cover to reset the fault; If the product is still faulty Product must be returned to factory for troubleshooting ATyS g M - 542933D - SOCOMEC...
Page 54
CORPORATE HQ CONTACT: SOCOMEC SAS 1-4 RUE DE WESTHOUSE 67235 BENFELD, FRANCE www.socomec.com 542933D...