4.2 Reinitialize on parameterization download

4.2
Reinitialize on parameterization download
Each time parameterization of the F-module occurs, reinitialization of internal module states
is required. This means that internal module states are equivalent to power-up states.
Reinitializing results in the following changes in the module:
• Process image status and event bits are reset
• Counter value is reinitialized to the start value
• Measured value calculations are reinitialized
• Process image command enables are reset
• Safety monitoring intermediate values are reset (for example, intermediate values
associated with SOS, SDI, and SLS calculations)
In addition to a user commanded download of parameters from STEP 7 (TIA Portal),
parameters will be downloaded, and the counter module will be reinitialized in the following
circumstances:
• Power cycling of the F-CPU
• Pull/Plug of the module
• Power cycling the 24V user power to the module
• Power cycling of the IM on a remote rack
• Pull/Plug of the PROFInet cable to the IM remote rack