Interrupts/diagnostic messages
6.4 Diagnostic messages
Diagnostics alarm
No pulses detected
F-address memory not
accessible
No valid F-address availa-
ble
Module is defective
Watchdog tripped
Undertemperature
78
Fault
code
16#030A
The expected number of pulses was not
received within a given revolution, where
the revolution is determined by the mod-
ule receiving an active N signal event.
Possible causes:
•
There is a faulty N signal.
•
The "Pulses per revolution" configura-
tion does not match the encoder's
pulses per revolution.
•
The module is configured to use the N
signal, but the encoder does not use
an N signal or there is a wire break.
•
There is noise on the N signal line.
16#030D
The F-source address and F-destination
address stored in the coding element
cannot be accessed.
16#030E
The electronic coding element contains
an invalid F-address.
16#0100
Possible causes:
•
Impermissibly high electromagnetic
interference is present.
•
The F-module has detected an internal
error and has reacted in a safety-
related manner.
•
Encoder frequencies received above
250kHz. In this situation, the module
is not defective.
16#0103
Possible causes:
•
Impermissibly high electromagnetic
interference is present.
•
The F-module has detected an internal
error and has reacted in a safety-
related manner.
16#0312
The minimum permissible temperature
limit has been violated.
Meaning
ET 200SP F-TM Count 1x1Vpp sin/cos HF (6ES7136-6CB00-0CA0)
Equipment Manual, V1.0, 01/2021, A5E47073911-AA
Solution
•
Check the N signal process wiring.
•
Check the parameter is set to
match the sinusoidal cycles per
revolution.
Verify that the coding element is pre-
sent or replace the coding element.
Assign a PROFIsafe address to the F-
module.
•
Eliminate the interference. The
module must then be pulled and
plugged, or the power switched
OFF and ON.
•
Ensure encoder frequencies below
200kHz and reapply power to the
module.
•
Replace defective F-module.
•
Operate the F-module within the
specified temperature range (see
Technical Specifications).
•
Once the temperature has in-
creased and returns to the specified
range, the F-module must be re-
moved and reinserted or the power
switched OFF and ON.