Interrupts/diagnostic messages
6.4 Diagnostic messages
Diagnostics alarm
No pulses detected
F-address memory not
accessible
No valid F-address availa-
ble
Module is defective
Watchdog tripped
Undertemperature
78
Fault
code
16#030A
The expected number of pulses was not
received within a given revolution, where
the revolution is determined by the mod-
ule receiving an active N signal event.
Possible causes:
There is a faulty N signal.
The "Pulses per revolution" configura-
tion does not match the encoder's
pulses per revolution.
The module is configured to use the N
signal, but the encoder does not use
an N signal or there is a wire break.
There is noise on the N signal line.
16#030D
The F-source address and F-destination
address stored in the coding element
cannot be accessed.
16#030E
The electronic coding element contains
an invalid F-address.
16#0100
Possible causes:
Impermissibly high electromagnetic
interference is present.
The F-module has detected an internal
error and has reacted in a safety-
related manner.
Encoder frequencies received above
250kHz. In this situation, the module
is not defective.
16#0103
Possible causes:
Impermissibly high electromagnetic
interference is present.
The F-module has detected an internal
error and has reacted in a safety-
related manner.
16#0312
The minimum permissible temperature
limit has been violated.
Meaning
ET 200SP F-TM Count 1x1Vpp sin/cos HF (6ES7136-6CB00-0CA0)
Equipment Manual, V1.0, 01/2021, A5E47073911-AA
Solution
Check the N signal process wiring.
Check the parameter is set to
match the sinusoidal cycles per
revolution.
Verify that the coding element is pre-
sent or replace the coding element.
Assign a PROFIsafe address to the F-
module.
Eliminate the interference. The
module must then be pulled and
plugged, or the power switched
OFF and ON.
Ensure encoder frequencies below
200kHz and reapply power to the
module.
Replace defective F-module.
Operate the F-module within the
specified temperature range (see
Technical Specifications).
Once the temperature has in-
creased and returns to the specified
range, the F-module must be re-
moved and reinserted or the power
switched OFF and ON.