Lincar Annarita 698 TP Using Instructions And Maintenance page 48

Residential space heating appliances with boiler fired by wood pellets
Table of Contents

Advertisement

Available languages

Available languages

CHIMNEY OR FLUE
The chimney or flue should have the following characteristics:
Well sealed from combustion products, impermeable and completely insulated as
normative condictions.
The flue has to be built with materials well suitable for normal mechanical stress,
heat, action of combustion products and their condenses.
The flow has to be vertical with deflections no higher that 45°.
A right distance from combustible or flammable material, insulated with an air
cavity or right insulator.
Internal round section, the square or rectangular section should have round corner
with a ray not less than 20 mm.
Internal section should be constant, free and indipendent.
Rectangluar section with sides ration max of 1,5.
All manufacturer instruction should be respected concerning the section and the
building characteristic of the chimney or flue. For particular section, deviation of
section or path a complete inspection of exhaust fumes system will be necessary.
It is advisable that the flue should be supplied with a „chamber „ for solid material
and condenses collection, placed under the flue throat and easy to be reached and
opened through a sealed „little door" for inspection.
In case of fire of chimney or flue, employ the right system to soffocate the flames
and call for firemen.
The chimney and gas tubes should be easy to log on for every maintenance and
cleaning operation.
EQUIPMENT CONNECTION TO FLUE AND EVACUATION OF COMBUSTION
PRODUCTS
The flue should receive the exhaust fumes from one only heating equipment.
It is possible to realise an equipment composed by a fireplace and a cooking oven with a
sole exhaust fumes point towards the chimney, for which the manufactures has to
provide the building characteristics of the duct of the exhaust fumes channel.
It is prohibited to connect in the same flue, a heating equipment and a suction hood.
It is prohibited to connect the exhaust pipe towards closed space even if it is in open air
The direct exhaust fumes has to be done ahead roof and the exhaust pipe should have the
above characteristics.
Horizontal tubes connection should have a min slope steep of 3% .
The gas tubes should be sealed against combustion products, in case of outside passage it
should be insulated.
The chimney and gas tubes should be easy to log on for every maintenance and cleaning
operation.
IT IT IT IT- - - - GB
48/120
GB- - - - FR
FR mod. Serie 698TP....
GB
GB
FR
FR

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Annarita 698 tp-saAnnarita 698 tpvtAnnarita 698 tp-savtAnnarita 698 tpvt steelAnnarita 698 tp-savt steel

Table of Contents