Incorrect Operation
The absolute position data does
not change, or the latest data
cannot be obtained.
6-2
Table 6.1 - Troubleshooting (continued)
Possible Causes
1. The absolute position data register
is being displayed by the I/O
monitoring function.
2. The absolute position data register
was defined as a single integer
number in the configuration task.
Actions to be Taken
1. It is prohibited to call up the
registers of the S-ABS II Card by
the I/O monitoring function.
2. Do not define the absolute
position data register as a single
integer numbers.