Selecting the output status if normally open or closed: [1404]
n. oPEn.
Relay 1 is normally open. [0]
n.CLoSE
Relay 1 is normally closed. [1]
Defaul: n. oPEn.
Select if positive or negative values have to be compared. [1405]
PoSIt..
The output is operative with positive weight. [0]
nEGAt.
The output is operative with negative weight. [1]
ALL:
The output is operative both with positive and negative weight. [2]
Default: PoSIt
Select whether only stable weight values are to be compared or also unstable: [1406]
norMAL
Output 1 is active with unstable weight. [0]
StAbLE
The output is active with stable weight. [1]
Default: norMAL
HySt. 1
SET-POINT 1 HYSTERESIS [1407]
Hysteresis value with respect to the set-point
Value: from 0 to Capacity
Default: 2
t1NEr1
SET-POINT 1 TIMING [1408]
Value of time, in tenths of a second, during which, when the weight value set is exceeded, the output
associated with set-point 1 remains enabled.
After this time, even if the weight value is still above the set-point, theoutput is automatically disabled.
The function is not active with programmed time equal to zero.
Values: from 000 to 999
Default: 0
dELAy1
SET-POINT 1 DELAY [1409]
Value of time, in tenths of a second, after which, when the set weight value is exceeded, the output
associated with set-point 1 is enabled.
The function is not active with programmed time equal to zero
Values: from 000 to 999
Default: 0