Electrical Wiring; Checking Procedures; When Using Switch Box - Hisense HYXE-J01H Service Handbook

Control switch
Table of Contents

Advertisement

HYXE-F01H
B.When Using Switch Box
M4 Screws
M4なべネジ
(現地調達品)
(Field-Supplied)

3. Electrical Wiring

Use a 0.3 to 0.75mm cable for connecting.The maximum total cable length is up 30m.If the total cable length exceeds 30m, use a twist pair cable
with shield tube(1P-0.75mm or more).In that case,the maximum total cable length is up to 500m.If using in combination with the control timer,the
allowable total cable length is up to 100m.The use of a cable other than that specified above can cause of malfunction due to the effects of noise.
Keep a distance more than 30cm between the transmission line (remote control switch cable and transmission wires) and power source of the indoor
units. If not, the air-conditioner may not operate properly or malfunction may occur due to effect of power source noise.
In case of simultaneously controlling multiple indoor units, set the refrigerant cycle numbers and addresses of the indoor units without overlapping.
Refer to the Tecnical Catalog II provided with each indoor unit when performing electrical wiring work between the remote control switch and indoor
units for setting the refrigerant cycle number and the indoor unit address.
No gap shall exist between the remote control switch cable and hole of the remote cotrol switch case. If there is a gap, cover the gap with vinyl tape.
If not, malfunction may occur due to entrance of water droplets or insects.

4. Checking Procedures

1)Turn ON the power supply for all the indoor units.
note
Although a portion of the LCD (liquid crystal display)
of the remote control switch may light immediately
power is turned on, this is not a malfunction.
after the
2)
For the models with the auto-address function,
wait for 3 minutes apporoximately. The addreing is
automatically performed.(There is a case that 5 mi-
inutes is required according to the setting condition.)
3) Enter running model
MODE
A/C
CHECK
Set the"TEST RUN"mode by pressing the
"MODE"and"CHECK"switch simultaneously
for more than 3 seconds
JIS box
(field-supplied)
ATTENTION : Always make sure to turn off the power of the indoor unit when performing electrical wiring
work. Performing electrical wiring work with the power on can damage the circuit boards of the indoor unit
and the remote control switch.
Remote control Switch
REMOCON REMOCON
M3.5 Screws
2
2
A."
B.The total number of the indoor units connected is
indicated on the LCD.
C.In case that the indicated number is not correct, the auto-address function is not performed corr-
ectly due to incorrect wiring, the electric noise or etc.
Turn OFF the power supply and correct the wiring after checking the following points;
(Do not repeat turning ON and OFF within 10 seconds.)
1. Power Supply for Indoor Unit is Not Turned ON or Incorrect Wiring.
2. Incorrect Connection of Connecting Cable between Indoor Units or
Incorrect Connection of Controller Cable.
3. Incorrect Setting of Rotary Switch and Dip Swiach
(The setting is overlapped.)on the Indoor Units PCB
D. Check to ensure that the "TEST RUN" mode is not set.
ATTENTION
F A N
UNIT
4) Canceling "TEST RUN" Mode
RESET
3)
Attach the remote control switch to the
holding bracket.Be careful not to pinch
the cable when attaching it.
4)
Remove the protection film from the liquid
crystal display.
Max. 16 indoor Units
Electrical Box
Electrical Box
of Indoor Unit
of Indoor Unit
Terminal Board
Terminal Board
M3.5
Screws
1P-0.75MM²
Twist Pair Cable with Shield Tube:
" is displayed on the LCD.
When "00" is indicated, the auto-address function may be performing.
Cancel the "TEST RUN" mode and set it again.
UNIT
1. When the unit is not operating,
press this switch.
20
Connect the terminals.
Remove the
protection film.
MODE
FAN
TIMER
GRILL
M3.5
Screws
or more
Example when 4 indoor Units are
connected.
UNIT
2. When the unit is operating,
RUN
2. When the unit is operating, press the RUN/STOP switch.
press this switch
STOP
LOU
VENTI
ON
OFF
CHECK
RESET

Hide quick links: