Hisense HYXE-J01H Service Handbook page 171

Control switch
Table of Contents

Advertisement

HCCS-H247R4C1E
Figure 2.2 meter adapter wiring diagram wiring specifications, see Table 2.1 Wiring Specification of meter
adapter.
No.
1
Other wiring specifications, see air conditioning adapter wiring specifications.
3. System installation configuration and debugging
3.1 IP address setting
3.1.1 Meter reading adapter IP settings
Meter Concentrator wiring and IP settings, see wiring and IP settings of air-conditioning adapter.
The factory default IP of meter adapter is set as:
IP address:192.168.1.101
Subnet mask: 255.255.255.0
Default adapter: 192.168.1.1
When used on site, the IP address of the meter adapter is re-set according to network configuration on the site.
Connect the server for setting directly to the air-conditioning adapter with a network cable, enter the IP
address of the air-conditioning adapter in the server web browser address bar: 192.168.1.101, press
carriage return, the browser displays the login screen as shown in Figure 3.1:
Figure 2.2 Wiring diagram of meter adapter
Table 2.1 Wiring Specification of meter adapter
Wiring type
Voltage
specification
between lines
RS485
DC 5V
communications
wiring
Figure 3.1 Setting and debugging login screen
Usage of wiring
For communication
with meter supporting
Modbus RTU of
Schneider Electric
must-have
.
162
Distance
Cable
of wiring
Specification
Within
0.75~1mm
1000m
a
2