13 Routine Maintenance
Re-spray the protective paint every 5 years to the inverter surface.

13.5 Replacing the Electrical Components

The electrical components inside the inverter must be replaced by the same
components from the same manufacturer and of the same model.
The model can be found on the marking of the inverter or the component itself.
If otherwise, contact Sungrow.
If the components needs to be replaced with products from other
manufacturers or of different model on site, a prior analysis and confirmation by
Sungrow is required.
Failure to follow this procedure may lead to physical injury or death and void all
warranty from Sungrow.

13.5.1 Safety Instructions

Strictly observe the instructions in this chapter to replace the fuse.
Any personal injury or property damage caused by the disobedience of this
chapter may void pertinent warranty claims from Sungrow.
Only qualified technical persons who have fully understood the description in
this chapter can perform the operations in this chapter.

13.5.2 Replacing DC Fuses

D D C C F F u u s s e e A A r r e e a a
The DC cabinet inside the inverter is equipped with DC fuses. The DC fuse area is shown
in the following figure A.