Safety Information - Siemens SINAMIC S120 Equipment Manual

Cooled chassis power units
Table of Contents

Advertisement

3.2

Safety information

Not observing fundamental safety instructions and residual risks
Not observing fundamental safety instructions and residual risks listed in Chapter 1 can
result in accidents with severe injuries or death.
• Comply with the fundamental safety instructions.
• When assessing the risk, take into account remaining risks.
High leakage currents when the protective conductor in the line feeder cable is
interrupted
The drive components conduct a high leakage current via the protective conductor.
Touching conductive parts when the protective conductor is interrupted can result in death
or serious injury.
• Ensure that the external protective conductor satisfies at least one of the following
Fire due to inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating with a risk for personnel through
smoke development and fire. This can also result in increased downtime and reduced
service lives for Motor Modules.
• Observe the ventilation clearances above, below, and in front of the Motor Modules,
Fire due to overheating when the total length of the power cables is exceeded
Overheating and a fire can result when the total length of the power cables is exceeded.
• Ensure that the total length of the power cables (motor feeder cables and DC link cables)
Air-Cooled Chassis Power Units - supplement to Motor Module 6SL3320-1TG41-5AA3
Equipment Manual, 10/2020, A5E50422764A
WARNING
WARNING
conditions:
– It has been installed so that it is protected against mechanical damage.
– For an individual core, it has a cross-section of at least 10 mm² Cu.
– If it is a conductor of a multi-conductor cable, it has a cross-section of at least 2.5
mm² Cu.
– It has a second protective conductor in parallel with the same cross-section.
– It complies with the local regulations for equipment with increased leakage current.
Cables laid within control cabinets or closed machine housings are considered to be
1)
adequately protected from mechanical damage.
WARNING
which are specified in the dimension drawings.
CAUTION
does not exceed the values specified in the technical data.
Motor Module Chassis 6SL3320-1TG41-5AA3
3.2 Safety information
1)
23

Advertisement

Table of Contents
loading

Table of Contents