Siemens SINAMIC S120 Equipment Manual page 66

Cooled chassis power units
Table of Contents

Advertisement

Cabinet design and EMC
5.3 Notes on control cabinet climate control
The opening cross-sections specified in the table refer in each case to one device. If more
than one device is installed in a cabinet, the opening cross-section increases accordingly. If
the required openings cannot be made in the cabinet, the devices must be distributed across
several cabinets which are separated from each other by means of partitions.
The warm air must be discharged via the top cover/hood or via side openings in the cabinet at
the level of the device top. The size of the opening cross-section must also be taken into
account here.
With degrees of protection higher than IP20 and if a hood is used, it may be necessary to use
an "active" hood. An "active" hood contains fans that blow the air current forwards. The hood
is closed, with the exception of the air outlet point.
If you choose an "active" hood, you must ensure that the fans are sufficiently powerful to
prevent air from accumulating in the cabinet. If air accumulates, the cooling capacity is
reduced. This can overheat and destroy the devices. The air capacity of the fans should at
least be equivalent to the device fan data.
Table 5- 5
Article number
Cooling air requirement
Min. opening cross-section in the control cabinet
intake opening
discharge opening
64
Volume flow rate, opening cross-sections
Air-Cooled Chassis Power Units - supplement to Motor Module 6SL3320-1TG41-5AA3
Motor Modules
6SL3320-
Equipment Manual, 10/2020, A5E50422764A
1TG41-5AA3
[m³/s]
1.08
[m²]
0.38
[m²]
0.38

Advertisement

Table of Contents
loading

Table of Contents